2016-07-12 15:24:451ST REVIEW MECHANICAL
 PERMIT #15100826
 7/12/16
  
 1) REFER TO TABLE 403.3 FBC-14 MECHANICAL: PROVIDE THE
 CONTROLS OPERATION FOR THE RESTROOM FANS. FOR
 INTERMITTENT USE THE FAN CAPACITIES SHOWN IN THE
 SCHEDULE ARE UNDERSIZED- 70 CFM PER WATER CLOSET OR
 URINAL IS REQUIRED.
  
 2) PROVIDE INSTALLATION DETAILS FOR THE EXHAUST FANS
 AND INDICATE THE TYPE AND GAGE OF EXHAUST DUCTWORK.
  
 3) SUBMIT FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE
 NOA'S FOR THE REST ROOM EXHAUST LOUVERS, AND THE
 VENTILATION LOUVERS FOR THE MEP AND THE TRAINING/FIRST
 AID ROOMS. ALL SUBMITTALS MUST SHOP DRAWING APPROVAL
 SIGNATURES BY THE EOR.
  
 4) PROVIDE VENTILATION CALCULATIONS FOR THE
 TRAINING/FIRST AID ROOMS IN COMPLIANCE WITH TABLE 403.3
  