| 2015-12-06 05:30:15 | 1) THE GAS HEATER SHALL HAVE A MINIMUM THERMAL |
| | EFFICIENCY OF 82%.THE SUBMITTED SPECIFICATION SHEET |
| | DOES NOT SHOW THIS REQUIREMENT. SUBMIT POOL HEATER |
| | SPECS THAT SHOW COMPLIANCE. 2014 FBC-ENERGY CODE |
| | SEC.R403.9.1.1.2ND REQUEST |
| | 2) GAS POOL HEATERS SHALL NOT HAVE CONTINUOUSLY BURNING |
| | PILOT LIGHTS.2014 FBC-ENERGY CODE SEC.R403.9.1.1. |
| | SUBMIT SPECIFICATIONS THAT SHOW COMPLIANCE. 2ND |
| | REQUEST. |
| | 3) IDENTIFY THE MODEL OF THE POOL HEATER TO BE |
| | INSTALLED ON THE MANUF. SPECIFICATIONS.2ND REQUEST |
| | 4) THE SUBMITTED GAS DRAWING SHOWS 3 HEATERS: 2 |
| | "HEATERS" @ 400,000 BTU'S AND ONE POOL HEATER AT |
| | 250,000 BTU'S. WHAT ARE THE TWO "HEATERS"? IF THEY ARE |
| | POOL HEATERS IDENTIFY THEM AS SUCH AND WHY ARE THERE 3 |
| | HEATERS WHEN THE POOL PLANS CALL OUT ONE. |
| | 5) THE GAS PLAN DOES NOT SHOW THE RANGE AND BBQ AS |
| | EXISTING IF THAT IS WHAT THEY ARE. IDENTIFY ON THE PLAN |
| | IF THEY ARE NEW AND TO BE INSTALLED UNDER THIS GAS |
| | PERMIT OR IF THEY ARE EXISTING. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 6) IDENTIFY THE BBQ OUTLET ON THE GAS RISER. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 7) SHOW THE BTU LOAD OF EACH APPLIANCE AT THE GAS |
| | OUTLET. THE PROPER SIZING FOR THE INDIVIDUAL SECTIONS |
| | OF PIPE CANNOT BE DETERMINED TO BE COMPLIANT WITHOUT |
| | THIS INFORMATION.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 8) THE SUBMITTED GAS PLAN SHOWS ONE POOL HEATER AS |
| | 250,000 BTU'S AND TWO OTHER " HEATERS " AS 400,000 |
| | BTU'S BUT THE POOL PLANS CALL OUT A 125,000 BTU GAS |
| | POOL HEATER AND ONE HEAT PUMP. AT THIS POINT, I HAVE |
| | ABSOLUTELY NO IDEA WHAT IS BEING INSTALLED ON THIS |
| | POOL. THE CONTRACTOR NEEDS TO COME IN AND STRAIGHTEN |
| | OUT THIS CONVOLUTED SUBMISSION AND SUBMIT TWO COPIES OF |
| | DOCUMENTS THAT SATISFY THE GAS REVIEW COMMENTS. |
| | |
| | ALSO, SEE PERMIT APPLICATION #15100811 |
| | |
| | |
| | ** NOTE: DO NOT SUBMIT CORRECTIONS FOR THE GAS UNLESS |
| | ALL ITEMS ARE CORRECTED. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |