| Notes |
| Date |
Text |
| 2015-10-27 09:02:34 | 1) SIZE ALL SECTIONS OF THE GAS PIPING DIAGRAM AND | | | CLEARLY SHOW THE TYPE OF PIPE BEING INSTALLED.WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 2) THE GAS DRAWING IS ILLEGIBLE.SUBMIT A GAS RISER THAT | | | IS CLEAR IN DETAIL AND SHOWS ALL PIPE SIZES, PIPE | | | MATERIALS AND BTU LOAD OF EACH APPLIANCE. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | 3) THE GAS HEATER SHALL HAVE A MINIMUM THERMAL | | | EFFICIENCY OF 82%.THE SUBMITTED SPECIFICATION SHEET | | | DOES NOT SHOW THIS REQUIREMENT. SUBMIT POOL HEATER | | | SPECS THAT SHOW COMPLIANCE. 2014 FBC-ENERGY CODE | | | SEC.R403.9.1.1. | | | 4) GAS POOL HEATERS SHALL NOT HAVE CONTINUOUSLY BURNING | | | PILOT LIGHTS.2014 FBC-ENERGY CODE SEC.R403.9.1.1. | | | SUBMIT SPECIFICATIONS THAT SHOW COMPLIANCE. | | | 5) IDENTIFY THE MODEL OF THE POOL HEATER ON THE MANUF. | | | SPECIFICATIONS THAT IS TO BE INSTALLED. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|