| 2015-10-24 02:36:10 | 1) THE NOTES ON THE PLAN STATE THIS IS A 2 PSI SYSTEM |
| | BUT THE TABLE YOU ARE REFERENCING FROM THE 2014 |
| | FBC-RES. ON THE PLANS IS FOR LESS THAN 2 PSI WITH A |
| | PRESSURE DROP OF 3.0 IN. W.C.. CLARIFY. |
| | 2) IF IT IS A 2 PSI SYSTEM, INDICATE THE CORRECT SIZING |
| | TABLE FOR THE SYSTEM ON THE PLAN.2014 FBC-FUEL GAS. |
| | SEC.402.2. |
| | 3) SIZE ALL SECTIONS OF THE PIPE ON THE RISER DIAGRAM. |
| | THE ONLY PIPE THAT IS SIZED IS THE 3/4" CSST TO THE |
| | RANGE, 2014 FGC SEC. 402.2. |
| | 4) SUBMIT MANUF. SPECS FOR THE DRYER AND RANGE. |
| | APPLIANCES SHALL BE LISTED AND LABELED. SEC. 301.3. |
| | 5) IF THE DRYER IS LOCATED IN A CLOSET, MAKEUP AIR |
| | SHALL BE PROVIDED. AN OPENING HAVING AN AREA OF NOT |
| | LESS THAN 100 SQUARE INCHES FOR MAKEUP AIR SHALL BE |
| | PROVIDED IN THE CLOSET ENCLOSURE OR MAKEUP AIR SHALL BE |
| | PROVIDED BY OTHER APPROVED MEANS. 2014 FGC SEC.304.1, |
| | 614.5. SHOW THE LOCATION OF THE DRYER ON THE FLOOR |
| | PLANS. |
| | 6) SHOW THE LOCATION OF ALL STEP-DOWN REGULATORS IF IT |
| | IS A 2 PSI SYSTEM. SHOW THE LOCATION OF THE REGULATOR |
| | VENTS AND THE SIZES.COMPLY W/ 2014 FGC SEC.410.2. & |
| | 410.3. |
| | 7) IF THE TANKLESS WATER HEATER IS REPLACING AN |
| | EXISTING STORAGE TANK TYPE, INDICATE SUCH ON THE PLANS. |
| | IF THE TANKLESS IS IN ADDITION TO AN EXISTING WATER |
| | HEATER, SUBMIT A WATER RISER DIAGRAM SHOWING WHERE THE |
| | COLD WATER SUPPLY IS COMING FROM.MINIMUM COLD WATER |
| | SUPPLY SHALL BE 3/4". |
| | 8) A SEPARATE PERMIT IS REQUIRED FOR ANY RELATED |
| | ELECTRICAL WORK THAT WILL BE DONE. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | ``````````````````````````````````````````````````````` |
| | ``````````````````````````````````````````````````````` |
| | ```````````````````````````` |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |