| Plan Review Notes For Permit 15100773 |
| Permit Number |
15100773 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-05 13:34:10 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15100773 | | | 11/5/2015 | | | | | | 1) DUE TO CHANGES IN THE FLOOR PLAN, THE AHU-1 IS NOW | | | SHOWN TO BE LOCATED ABOVE THE WOMEN'S TOILET ROOM | | | SUSPENDED CEILING. PLEASE REFER TO SECTION 306.1 AND | | | INDICATE HOW ACCESS FOR INSPECTION, SERVICE, REPAIR, | | | AND REPLACEMENT WILL BE ACCOMPLISHED WITHOUT REMOVING | | | PERMANENT CONSTRUCTION. | | | 2) SHOW THE AC CONDENSATE PIPING RUNS AND DISCHARGE | | | LOCATIONS. | | | 3) THE AC SYSTEM DATA FOR COOLING CAPACITY AND SEER | | | LISTED IN THE SCHEDULE ON M0.1 DOES NOT MATCH THE DATA | | | LISTED UNDER SYSTEM REPORT COMPLIANCE IN THE ENERGY | | | CONSERVATION FORM SUBMITTAL: PLEASE CORRECT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|