| 2016-01-04 06:53:21 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15100764 |
| | ADD: 1100 W. TECHNOLOGY PL. SUITE # 110 |
| | CONT: HEDRICK BROS. CONSTRUCION |
| | TEL: (561)689-8880 |
| | E-MAIL: ??????? |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. JAN. 04/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED PLANS INDICATES THIS TENANT SPACE IS A |
| | CHANGE OF OCCUPANCY FROM A F1 OCCUPANCY, A DRY CLEANING |
| | FACILITY WHERE THERE WAS A BOILER, NOT JUST A DROP OFF |
| | AND PICK UP FACILITY. PERMIT # 99111358 SHOULD A FULL |
| | SCALE DRY CLEANING FACILITY, THE NEW OCCUPANCY IS |
| | INDICATED AS A BUSINESS OCCUPANCY. SHEET A0.2 & M1.1 |
| | BOTH SHOW THIS SPACE TO NOW BE NON-CONDITIONED SPACE. |
| | |
| | PLEASE SHOW HOW THE BUSINESS/ STORAGE OCCUPANCY WILL |
| | MEET THE CODE SECTION OF: |
| | 2014 FBC-B 1203.4. 1203.4 NATURAL VENTILATION. NATURAL |
| | VENTILATION OF AN OCCUPIED SPACE SHALL BE THROUGH |
| | WINDOWS, DOORS, LOUVERS OR OTHER OPENINGS TO THE |
| | OUTDOORS. THE OPERATING MECHANISM FOR SUCH OPENINGS |
| | SHALL BE PROVIDED WITH READY ACCESS SO THAT THE |
| | OPENINGS ARE READILY CONTROLLABLE BY THE BUILDING |
| | OCCUPANTS. |
| | |
| | 1203.4.1 VENTILATION AREA REQUIRED. THE OPENABLE AREA |
| | OF THE OPENINGS TO THE OUTDOORS SHALL BE NOT LESS THAN |
| | 4 PERCENT OF THE FLOOR AREA BEING VENTILATED. |
| | |
| | |
| | |
| | |
| | 2) AS PREVIOSLY NOTED IN THE 1ST REVIEW, THIS IS A |
| | CHANGE OF OCCUPANCY FROM A (F-1 FACTORY) TO A BUSINESS |
| | OCCUPANCY, WHICH REQUIRES COMPLIANCE WITH SECTION: |
| | |
| | C101.4.4 OF THE 2014 FBC-ENERGY CONSERVATION CODE. |
| | C101.4.4 CHANGE IN OCCUPANCY OR USE. SPACES UNDERGOING |
| | A CHANGE IN OCCUPANCY THAT WOULD RESULT IN AN INCREASE |
| | IN DEMAND FOR EITHER FOSSIL FUEL OR ELECTRICAL ENERGY |
| | SHALL COMPLY WITH THIS CODE. WHERE THE USE IN A SPACE |
| | CHANGES FROM ONE USE IN TABLE C405.5.2(1) OR (2) TO |
| | ANOTHER USE IN TABLE C405.5.2(1) OR (2), THE INSTALLED |
| | LIGHTING WATTAGE SHALL COMPLY WITH SECTION C405.5. |
| | |
| | 3) COMPLIED. N/A. |
| | |
| | 4)COMPLIED. N/A. |
| | |
| | 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |