| 2015-11-19 17:07:36 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | 1. FBC-E402.4.8, ALL RECESSED LUMINAIRES INSTALLED IN |
| | THE BUILDING'S THERMAL ENVELOPE SHALL BE IC RATED AND |
| | SEALED TO LIMIT AIR LEAKAGE BETWEEN THE CONDITIONED AND |
| | THE NON-CONDITIONED SPACE. |
| | 2. FBC-E405.2.2.2, OCCUPANCY SENSORS SHALL BE INSTALLED |
| | IN ALL BATHROOMS 300 SQ. FT. OR LESS. |
| | 3. FBC-B714.3, ALL OUTLETS AND/OR ELECTRICAL PANELS |
| | INSTALLED IN A FIRE RATED WALL SHALL COMPLY AS |
| | INDICATED. |
| | 4. NEC210.63, THERE SHALL BE A 15 - 20 AMP SERVICE |
| | OUTLET WITHIN 25' OF THE HVAC EQUIPMENT. |
| | 5. NEC300.5(B), THE INTERIOR OF A RACEWAY INSTALLED |
| | UNDERGROUND SHALL BE CONSIDERED A WET LOCATION AND |
| | THEREFORE THE FEEDER CONDUCTORS SHALL BE LISTED |
| | ACCORDINGLY. |
| | 6. NEC410.36, LUMINAIRES INSTALLED ON FRAMING MEMBERS |
| | OF A SUSPENDED CEILING SHALL BE SECURELY FASTENED TO |
| | THE CEILING FRAMING MEMBERS BY MECHANICAL MEANS. |
| | 7. NEC600.5, EVERY COMMERCIAL ESTABLISHMENT SHALL HAVE |
| | AT EVERY ENTRY ACCESSIBLE TO PEDESTRIANS A DEDICATED |
| | SIGN OUTLET. |
| | 8. NEC700.12(F), ALL EMERGENCY AND EXIT LIGHTS SHALL BE |
| | CONNECTED TO THE ELECTRICAL CIRCUIT FOR THE AREA IN |
| | WHICH THEY ARE LOCATED. A DEDICATED EMERGENCY LIGHT |
| | CIRCUIT IS NOT ALLOWED BY CODE UNLESS THERE IS A |
| | MINIMUM OF THREE DIFFERENT CIRCUITS FOR THE AREA. |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |