| 2015-11-02 13:50:51 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15100764 |
| | ADD: 1100 W. TECHNOLOGY PL. SUITE # 110 |
| | CONT: HEDRICK BROS. CONSTRUCION |
| | TEL: (561)689-8880 |
| | E-MAIL: ??????? |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. NOV. 02/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED PLANS INDICATES THIS TENANT SPACE IS A |
| | CHANGE OF OCCUPANCY FROM A F1 OCCUPANCY, A DRY CLEANING |
| | FACILITY WHERE THERE WAS A BOILER, NOT JUST A DROP OFF |
| | AND PICK UP FACILITY. PERMIT # 99111358 SHOULD A FULL |
| | SCALE DRY CLEANING FACILITY, THE NEW OCCUPANCY IS |
| | INDICATED AS A BUSINESS OCCUPANCY. SHEET A0.2 & M1.1 |
| | BOTH SHOW A NEW |
| | RTU TO BE INSTALLED ON THE ROOF. |
| | 2014 ENERGY CODE C101.4.5 CHANGE IN SPACE CONDITIONING. |
| | ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME |
| | CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO |
| | FULL COMPLIANCE WITH THIS CODE. PLEASE PROVIDE HOW |
| | COMPLIANCE WILL BE ACHIEVED? |
| | |
| | 2014 C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL |
| | COMPLY WITH ONE OF THE FOLLOWING: |
| | 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. |
| | 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND |
| | C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY |
| | WITH EITHER SECTION C406.2, C406.3 OR C406.4. |
| | 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, |
| | C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE |
| | BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 |
| | PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING. |
| | NOTE THE OVERHEAD DOOR MAYBE REQUIRED TO BE INSULATED, |
| | DEPENDING ON THE EMERGY CALCULATIONS. |
| | |
| | 2A) THE PLANS DO NOT INDICATE HOW THE ROOF IS GOING TO |
| | BE FRAMED IN AROUND THE NEW ROOF TOP HOLE FOR THE NEW |
| | RTU. PLEASE PROVIDE FRAMING MEMBERS REQUIRED, TYPE OF |
| | MATERIALS, BAR JOIST WILL REQUIRE STIFFENERS IN THE BAR |
| | JOIST, FRAMING DETAILS, AND PLEASE PROVIDE HOW THE NEW |
| | ROOF TOP CURB WILL BE ANCHORED TO THE BAR JOIST AND |
| | FRAMING MEMBERS. PLEAS ALSO PROVIDE A PRODUCT APPROVAL |
| | FOR THE NEW ROOF TOP CURB FOR THE RTU UNIT. MWFRS MAIN |
| | WIND FORCE RESISSTING SYSTEM AND 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF TOP CURBS |
| | |
| | 2B) THE PLANS DO NOT INDICATE HOW THE RTU ROOF TOP UNIT |
| | IS GOING TO BE ATTACHED TO THE ROOF TOP CURB TO RESIST |
| | LATERAL SLIDDING AND THE MOMENT OF OVERTURNING. PLEASE |
| | PROVIDE DETAIL. 2014 FBC-B 1609.6.4.4.1. |
| | |
| | 3) THW PLANS DO NOT INDICATE THE ROOF ELEVATION NOR IF |
| | THERE IS A PAREPET AND THE HEIGHT OF THE PAREPET. |
| | APERMANENT LADDER MAYBE REQUIRED FOR ROOF TOP ACCESS, |
| | PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B ? 1509.6.4 |
| | EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED |
| | STRUCTURES. |
| | WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE |
| | INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT |
| | EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE |
| | PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| | EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| | THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH |
| | ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS |
| | GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON |
| | ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN |
| | 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| | PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED |
| | ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN |
| | CRITERIA: |
| | 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR |
| | ROOF EDGE NOT LESS THAN 30 INCHES (762 MM). |
| | 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14 |
| | INCHES (356 MM) ON CENTER. |
| | 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN |
| | 6-INCHES (152 MM) DEEP. |
| | 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM) |
| | BETWEEN RAILS. |
| | 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM) |
| | DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND |
| | (136.1 KG) LOAD. |
| | 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE |
| | PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF |
| | WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2). |
| | 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY |
| | APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE |
| | REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610 |
| | MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR |
| | SERVICE PLATFORMS |
| | |
| | 4) THE OTHER ISSUE MAYBE THE ARCHITECTURAL PLANS DO NOT |
| | PROVIE THE HEIGHT OF THE PARAPET WALL, ZONING MAY |
| | REQUIRE THE A/C RTU ROOF TOP UNIT TOBE SCREENED. IF SO |
| | PLEASE PROVIDE HOW THE FRAMEWORK WILL BE ATTACHED TO |
| | THE MAINWIND FORCE RESISTING SYSTEM AND HOW THE WIND |
| | SCREEN IS TO BE ATTACHED TO THE FRAME. WHAT WIND DESIGN |
| | PERAMETERS ARE GOING TO BE USED TO FORMULATE THE |
| | RELEASE OF THE FABRIC IN HIGH WIND EVENTS? |
| | 1609.6.4.4.1/ 3105.4.2.1. |
| | |
| | 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |