Plan Review Notes For Permit 15100709
Permit Number 15100709
Review Stop P
Sequence Number 3
Notes
Date Text
2015-10-31 06:06:49THE DISCHARGE FROM THE EVAPORATORS IN COOLERS WHERE
 FOOD IS BEING STORED TO A CONDENSATE WELL RAISES
 CONCERNS. PLEASE REFER TO 2010 FBC-PLUMBING, SEC. 801.2
 - PROTECTION. ALSO, REFER TO SECS.802.1.1, 802.2,
 802.3.I CANNOT APPROVE THIS METHOD OF DISCHARGE. THE
 EVAPOEATORS SHALL DRAIN TO THE SANITARY SYSTEM PER THE
 ABOVE NOTED CODE SECTIONS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  