| Notes |
| Date |
Text |
| 2016-06-09 16:13:54 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15100707 | | | 6/9/16 | | | | | | 1) I AM NOT AGREEING WITH THE 81 DEGREE COOLING DESIGN | | | TEMPERATURE FOR WEST PALM BEACH AS SHOWN ON THE AC LOAD | | | CALCULATIONS. AS PREVIOUSLY NOTED, TABLE 1A OF ACCA | | | MANUAL N LISTS THE COOLING DRYBULB TEMP FOR WPB AT 90 | | | DEGREES. PLEASE ADJUST THE CALCULATIONS OR SUBMIT THE | | | DESIGN WITH AS AN ALTERNATEMETHOD ACCOMPANIED BY A | | | SIGNED AND SEALED LETTER FROM THE EOR. | | | | | | 2) BASED ON THE DRAWING, THE FRONT DOOR OF THE BUILDING | | | APPEARS TO BE FACING EAST, HOWEVER THE AC CALCULATIONS | | | ARE INDICATING NORTH | | | | | | 3) PLEASE REVIEW AND REVISE THE ENERGY GAUGE COMPLIANCE | | | CHECKLIST- SOME OF THE BOXES CHECKED "YES" DO NOT | | | APPEAR APPLICABLE TO THIS PROJECT. | | | | | | 4) SHEET A3 INDICATES A WOOD DOOR ACCESS DOOR TO THE AC | | | CLOSET IN OFFICE 2. AS PREVIOSULY NOTED, A | | | NON-COMBUSTIBLE DOOR IS REQUIRED PER SECTION C403.2.7.2 | | | FBC-14 ENERGY CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|