| 2016-06-20 10:18:23 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15100707 |
| | ADD: 831 BELVEDERE RD. |
| | CONT: AJS BUILDING & RENOVATIONS, INC. |
| | TEL: (407)298-9700 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 4TH REVIEW |
| | DATE: MON. JUNE 20 /2016 |
| | ACTION: DENIED |
| | |
| | 1-3) COMPLIED |
| | |
| | 4) NEW COMMENT. THIS COMMENT DEALS WITH THE SAME ISSUE, |
| | JUST REPHRASED. I'VE SPOKEN WITH OUR ASSISTANT BUILDING |
| | OFFICIAL ABOUT HOW I'VE WORDED THIS COMMENT, HE AGRESS |
| | THAT A ROOFING PRODUC APPROVAL WOULD NOT BE REQUIRED |
| | FOR THE ANCHORING OF THE A/C STAND TO THE CONCRETE |
| | ROOF. HE BELIEVES THERE SHOULD BE A DETAIL SHOWING HOW |
| | THE ROOF WILL BE SEALED WHERE THE PENETRATION IS MADE |
| | FOR THE ANCHORING OF THE STAND INTO THE CONCRETE ROOF |
| | DECK. TYPICAL DETAIL MAY INCLUDE A PITCH CUP SHOW IF |
| | THE HORIZONTAL LEG PORTION IS BENT IN OR BENT OUT. THE |
| | TYPE OF MATERIAL AND GAUGE OF THE PITCH CUP. IF THE |
| | HORIZONTAL LEG OF THE PITCH CUP IS COPPER, HOW IT WILL |
| | BE ISOLATED FROM THE ALUMINUM A/C STAND LEG AND ANCHOR |
| | PLATE. TYPE AND SIZE OF ANCHOR FOR BOTH THE PITCH CUP |
| | AND A/C STAND. |
| | TYPE OF MATERIAL TO FILL THE PITCH CUP AND THE MATERIAL |
| | TO SEAL THE ROOFING ON THE OUTSIDE OF THE PITCH CUP. |
| | PLEASE PROVIDE A DIAGRAM WITH THIS INFORMATION. |
| | 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| | CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| | DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| | FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND |
| | RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED. |
| | |
| | PREVIOUS COMMENT. 2ND REQUEST. SEMI-COMPLIED. THE |
| | ROOFING PRODUCT APPROVAL WAS SUBMITTED, THE CONTRACTOR |
| | NOR THE DESIGNER OF RECORD HAS IDENTIFIED THE ROOFING |
| | SUB-SYSTEM TO BE INSTALLED AND THE ASSOCIATED |
| | PRESSURES, SEE MAXIMUM DESIGN PRESSURES AND |
| | LIMITATIONS, EITHER 7 OR 9. 107.3.4.1 THOSE PRODUCTS |
| | WHICH ARE REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5-8) COMPLIED |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |