2016-06-20 10:18:23BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100707
 ADD: 831 BELVEDERE RD.
 CONT: AJS BUILDING & RENOVATIONS, INC.
 TEL: (407)298-9700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: MON. JUNE 20 /2016
 ACTION: DENIED
  
 1-3) COMPLIED
  
 4) NEW COMMENT. THIS COMMENT DEALS WITH THE SAME ISSUE,
 JUST REPHRASED. I'VE SPOKEN WITH OUR ASSISTANT BUILDING
 OFFICIAL ABOUT HOW I'VE WORDED THIS COMMENT, HE AGRESS
 THAT A ROOFING PRODUC APPROVAL WOULD NOT BE REQUIRED
 FOR THE ANCHORING OF THE A/C STAND TO THE CONCRETE
 ROOF. HE BELIEVES THERE SHOULD BE A DETAIL SHOWING HOW
 THE ROOF WILL BE SEALED WHERE THE PENETRATION IS MADE
 FOR THE ANCHORING OF THE STAND INTO THE CONCRETE ROOF
 DECK. TYPICAL DETAIL MAY INCLUDE A PITCH CUP SHOW IF
 THE HORIZONTAL LEG PORTION IS BENT IN OR BENT OUT. THE
 TYPE OF MATERIAL AND GAUGE OF THE PITCH CUP. IF THE
 HORIZONTAL LEG OF THE PITCH CUP IS COPPER, HOW IT WILL
 BE ISOLATED FROM THE ALUMINUM A/C STAND LEG AND ANCHOR
 PLATE. TYPE AND SIZE OF ANCHOR FOR BOTH THE PITCH CUP
 AND A/C STAND.
 TYPE OF MATERIAL TO FILL THE PITCH CUP AND THE MATERIAL
 TO SEAL THE ROOFING ON THE OUTSIDE OF THE PITCH CUP.
 PLEASE PROVIDE A DIAGRAM WITH THIS INFORMATION.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
  
 PREVIOUS COMMENT. 2ND REQUEST. SEMI-COMPLIED. THE
 ROOFING PRODUCT APPROVAL WAS SUBMITTED, THE CONTRACTOR
 NOR THE DESIGNER OF RECORD HAS IDENTIFIED THE ROOFING
 SUB-SYSTEM TO BE INSTALLED AND THE ASSOCIATED
 PRESSURES, SEE MAXIMUM DESIGN PRESSURES AND
 LIMITATIONS, EITHER 7 OR 9. 107.3.4.1 THOSE PRODUCTS
 WHICH ARE REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5-8) COMPLIED
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  