| 2016-04-15 16:16:15 | 3RD REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15100707 |
| | 3RD MECHANICAL REVIEW |
| | |
| | 1) THE SUBMITTED AC CALCULATIONS ARE BASED ON AN |
| | INCORRECT DRY BULB TEMPERATURE OF 81 DEGREEES FOR WEST |
| | PALM BEACH. DRY BULB TEMPERATURE PER ACCA MANUAL N IS |
| | 91 DEGREES. |
| | 2) THE AC CALCS ARE BASED ON THE FRONT DOOR FACING |
| | NORTH, HOWEVER THE FRONT DOOR FOR THE NEW OCCUPANCY |
| | APPEARS TO BE FACING SOUTHEAST. |
| | 3) PLEASE COMPLETE THE MANDATORY REQUIREMENTS CHECKLIST |
| | ON PAGE 7 OF THE ENERGY EFFICIENCY SUBMITTAL, AND |
| | SUBMIT THE INPUT DATA REPORT AS NOTED ON PAGE 1. |
| | 4) THE WIND LOAD DESIGN CRITERIA ON SHEET M1 IS |
| | INCOMPLETE: PROVIDE THE BASIC WIND SPEED, EXPOSURE |
| | CATEGORY, AND IMPORTANCE FACTOR PER SECTION 1609 FBC-14 |
| | BUILDING. PLEASE NOTE THE NOA #98-126.01 IS NOT A VALID |
| | NOA NUMBER. PLEASE PROVIDE THE CORRECT NUMBER ON THE |
| | PLAN AND TWO COPIES OF THE DOCUMENT REVIEWED AND |
| | APPROVED WITH SIGNATURE BY THE EOR. |
| | 5) SHEET A3 INDICATES A WOOD-LOUVERED AC CLOSET DOOR, |
| | AND M1 INDICATES A RETRURN AIR GRILL IONTO THE CLOSET |
| | WITH NO DOORS. PLEASE NOTE THAT IF A LOUVERED DOOR IS |
| | TO BE USED IT MUST BE NON-COMBUSTIBLE- SECTIONS |
| | C403.2.7.2 & C403.2.7.3 FBC-ENERGY CONSERVATION. |
| | 6) M1: THE CORRIDOR CANNOT BE USED AS A RETURN DUCT PER |
| | SECTION 601.2. PLEASE REMOVE THE TRANSFER AND PROVIDE A |
| | DUCTED RETRUN. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |