Plan Review Notes
Plan Review Notes For Permit 15100707
Permit Number 15100707
Review Stop M
Sequence Number 3
Notes
Date Text
2016-04-15 16:16:153RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100707
 3RD MECHANICAL REVIEW
  
 1) THE SUBMITTED AC CALCULATIONS ARE BASED ON AN
 INCORRECT DRY BULB TEMPERATURE OF 81 DEGREEES FOR WEST
 PALM BEACH. DRY BULB TEMPERATURE PER ACCA MANUAL N IS
 91 DEGREES.
 2) THE AC CALCS ARE BASED ON THE FRONT DOOR FACING
 NORTH, HOWEVER THE FRONT DOOR FOR THE NEW OCCUPANCY
 APPEARS TO BE FACING SOUTHEAST.
 3) PLEASE COMPLETE THE MANDATORY REQUIREMENTS CHECKLIST
 ON PAGE 7 OF THE ENERGY EFFICIENCY SUBMITTAL, AND
 SUBMIT THE INPUT DATA REPORT AS NOTED ON PAGE 1.
 4) THE WIND LOAD DESIGN CRITERIA ON SHEET M1 IS
 INCOMPLETE: PROVIDE THE BASIC WIND SPEED, EXPOSURE
 CATEGORY, AND IMPORTANCE FACTOR PER SECTION 1609 FBC-14
 BUILDING. PLEASE NOTE THE NOA #98-126.01 IS NOT A VALID
 NOA NUMBER. PLEASE PROVIDE THE CORRECT NUMBER ON THE
 PLAN AND TWO COPIES OF THE DOCUMENT REVIEWED AND
 APPROVED WITH SIGNATURE BY THE EOR.
 5) SHEET A3 INDICATES A WOOD-LOUVERED AC CLOSET DOOR,
 AND M1 INDICATES A RETRURN AIR GRILL IONTO THE CLOSET
 WITH NO DOORS. PLEASE NOTE THAT IF A LOUVERED DOOR IS
 TO BE USED IT MUST BE NON-COMBUSTIBLE- SECTIONS
 C403.2.7.2 & C403.2.7.3 FBC-ENERGY CONSERVATION.
 6) M1: THE CORRIDOR CANNOT BE USED AS A RETURN DUCT PER
 SECTION 601.2. PLEASE REMOVE THE TRANSFER AND PROVIDE A
 DUCTED RETRUN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  