2016-01-14 16:01:562ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100707
 01/14/16
  
 COMMENTS #1, 2, AND 4 FROM THE 1ST REVIEW STILL EXIST.
 I AM HAVE ATTACHED THEM BELOW. PLEASE NOTE THAT THE M-1
 MECHANICAL SHEETS WERE NOT INSERTED INTO THE REVISED
 PLAN SETS- PLEASE ADD THE REQUIRED SHEETS.
 1) THE PROPOSED PROJECT IS CLASSIFIED AS A RENOVATED
 BUILDING IN ACCORDANCE WITH SECTION C202 FBC-14 ENERGY
 CONSERVATION, AND THEREFORE SHALL BE IN COMPLIANCE WITH
 THE CURRENT CODE PER SECTION C101.4.3. PLEASE SUBMIT
 TWO COPIES OF COMPLIANCE DOCUMENTATION USING EITHER THE
 PRESCRIPTIVE OR PERFORMANCE BASED COMPLIANCE PATH AS
 OUTLINED IN SECTION C101.5.1.
 (PLEASE NOTE THAT THE NARRATIVE RESPONSE IS INDICATING
 A PREVIOUSLY CONDITIONED BUILDING, HOWEVER THIS IS NOT
 THE ISSUE).
 2) REFER TO SECTION C403.2.1 AND SUBMIT COOLING AND
 HEATING CALCULATIONS FOR THE NEW 3-TON AC SYSTEM IN
 ACCORDANCE WITH THE PROCEDURES DESRIBED IN THE
 ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL N.
 ( PLEASE NOTE THE NARRATIVE RESPONSE INDICATES THE
 CALCULATIONS HAVE BEEN PROVIDED BUT THEY WERE NOT
 SUBMITTED).
 4) SITE SPECIFIC WINDLOAD ENGINEERING IS REQUIRED FOR
 ROOFTOP AC UNITS IN COMPLIANCE WITH SECTION 301.15. THE
 ENGINEER OF RECORD MUST PROVIDE THE WIND LOAD DESIGN
 CRITERIA AND DESIGN PRESSURES ON THE PLAN, AND SUBMIT
 REVIEWED AND APPROVED NOA'S OR PRODUCT APPROVALS FOR
 THE ROOF STAND AND CLIPS.
 (PLEASE NOTE THAT THE NOA WAS SUBMITTED HOWEVER THE
 REQUESTED WIND DESIGN CRITERIA WAS NOT INDICATED ON THE
 PLANS AS REQUESTED).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER