Notes
Date Text
2016-02-16 14:00:08PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 ELECTRICAL SERVICE AND WIRE SIZES DO NOT CORRESPOND TO
 THE OVERCURRENT PROTECTION PROVIDED AT THE PANELS. THE
 MAXIMUM LOAD ON A 1/0 CONDUCTOR IS 150 AMPERES. PLANS
 SHOW PANELS WITH 200 AMPERE MAIN BREAKERS BUT A SERVICE
 DISCONNECT OF 100 AMPERES. PLEASE CLARIFY. NEC 215.5
  
 CLARIFY IF THE NEW SERVICE WILL BE PART OF THE EXISTING
 OVERHEAD SERICE OR A NEW UNDERGROUND SERVICE AS
 INDICATED ON THE PLANS. NEC 215.5
  
 FEEDERS TO THE PANELBOARDS SHOWN ARE 2 WIRE SINGLE
 PHASE BUT THE PANEL DIRECTORY SUGGESTS THREE PHASE
 PANELS ARE PROPOSED. LOADS HAVE NOT BEEN BALANCED.
 PLEASE CLARIFY. NEC 215.5
  
 NEUTRAL FEEDER SHOWN ARE NOT FULL SIZE. PROVIDE AN
 CALCULATION FOR THE UNBALANCED PORTION OF THE
 ELECTRICAL LOAD WHICH THE NEUTAL FEEDERS WILL CARRY.
 NEC 220.61
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 ELECTRIC SERVICE AND ELECTRIC PANELS. NEC 110.9, 110.10
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.16, 110.22
  
 PROVIDE A DIMENSIONED DETAIL FOR THE ELECTRIC EQUIPMENT
 SHOWING THE LOCATION AND ALL SAFETY CLEARANCES WITH
 ADEQUATE HEAD ROOM. NEC 110.26
  
 PROVIDE A 20 AMPERE DEDICATED SIGN CIRCUIT. NEC 600.5
  
 PROVIDE A INTERSYSTEM BONDING BAR AT THE ELECTRICAL
 SERVICE. NEC 250.94
  
 THE GROUNDING ELECTRODE WITH A RIDGIT CONDUIT SLEEVE
 REQUIRES BONDING AT BOTH ENDS. NEC250.64(E)
  
 PROVIDE LIGHTING CONTROLS FOR ENERGY CONSERVATION SO
 THAT THE INTERIOR AND EXTERIOR LIGHTING CONTROLS
 PROVIDED FUNCTION IN ACCORDANCE WITH THE FLORIDA ENERGY
 CODE. EXTERIOR AUTOMATIC CONTROLS SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. FBC ENERGY
 CONSERVATION C405.2
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION C405.2
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER