| 2016-02-16 14:00:08 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | ELECTRICAL REVIEW COMMENTS. |
| | |
| | ELECTRICAL SERVICE AND WIRE SIZES DO NOT CORRESPOND TO |
| | THE OVERCURRENT PROTECTION PROVIDED AT THE PANELS. THE |
| | MAXIMUM LOAD ON A 1/0 CONDUCTOR IS 150 AMPERES. PLANS |
| | SHOW PANELS WITH 200 AMPERE MAIN BREAKERS BUT A SERVICE |
| | DISCONNECT OF 100 AMPERES. PLEASE CLARIFY. NEC 215.5 |
| | |
| | CLARIFY IF THE NEW SERVICE WILL BE PART OF THE EXISTING |
| | OVERHEAD SERICE OR A NEW UNDERGROUND SERVICE AS |
| | INDICATED ON THE PLANS. NEC 215.5 |
| | |
| | FEEDERS TO THE PANELBOARDS SHOWN ARE 2 WIRE SINGLE |
| | PHASE BUT THE PANEL DIRECTORY SUGGESTS THREE PHASE |
| | PANELS ARE PROPOSED. LOADS HAVE NOT BEEN BALANCED. |
| | PLEASE CLARIFY. NEC 215.5 |
| | |
| | NEUTRAL FEEDER SHOWN ARE NOT FULL SIZE. PROVIDE AN |
| | CALCULATION FOR THE UNBALANCED PORTION OF THE |
| | ELECTRICAL LOAD WHICH THE NEUTAL FEEDERS WILL CARRY. |
| | NEC 220.61 |
| | |
| | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE |
| | ELECTRIC SERVICE AND ELECTRIC PANELS. NEC 110.9, 110.10 |
| | |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING |
| | MEANS. NEC 110.16, 110.22 |
| | |
| | PROVIDE A DIMENSIONED DETAIL FOR THE ELECTRIC EQUIPMENT |
| | SHOWING THE LOCATION AND ALL SAFETY CLEARANCES WITH |
| | ADEQUATE HEAD ROOM. NEC 110.26 |
| | |
| | PROVIDE A 20 AMPERE DEDICATED SIGN CIRCUIT. NEC 600.5 |
| | |
| | PROVIDE A INTERSYSTEM BONDING BAR AT THE ELECTRICAL |
| | SERVICE. NEC 250.94 |
| | |
| | THE GROUNDING ELECTRODE WITH A RIDGIT CONDUIT SLEEVE |
| | REQUIRES BONDING AT BOTH ENDS. NEC250.64(E) |
| | |
| | PROVIDE LIGHTING CONTROLS FOR ENERGY CONSERVATION SO |
| | THAT THE INTERIOR AND EXTERIOR LIGHTING CONTROLS |
| | PROVIDED FUNCTION IN ACCORDANCE WITH THE FLORIDA ENERGY |
| | CODE. EXTERIOR AUTOMATIC CONTROLS SHALL BE CAPABLE OF |
| | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS |
| | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. FBC ENERGY |
| | CONSERVATION C405.2 |
| | |
| | PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN |
| | WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY |
| | CODE REQUIREMENTS. FBC ENERGY CONSERVATION C405.2 |
| | |
| | ROBERT LECKY |
| | ELECTRICAL PLANS EXAMINER |
| | 561-373-3701 |
| | [email protected] |
| | |