2016-01-20 07:52:05BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100707
 ADD: 831 BELVEDERE RD.
 CONT: AJS BUILDING & RENOVATIONS, INC.
 TEL: (407)298-9700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JAN. 20/2016
 ACTION: DENIED
  
 1) 2ND REQUEST. RESPONSE INDICATES THE DESIGN PRESSURES
 FOR NEW WINDOWS AND DOORS THE CALCULATIONS ARE
 ATTACHED. THE WIND DESIGN CRITERIA AND ASSOCIATED
 PRESSURES ARE CORRECT. THE WIND DESIGN CRITERIA AND
 PRESSURES ARE FROM VVS ENGINEERING; THEY ARE NOT SIGNED
 NOR SEALED. . PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 EFFECTIVE DATE 05/06/2009
  
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW. THE ENGINEER OF RECORD
 JOHN STOPPI P. E. SHOULD APPLY HIS SHOP DRAWING STAMP
 REVIEWED AND APPROVED.
  
  
 ORIGINAL COMMENT # 1. SHEET A4 BUILDING EAST ELEVATION
 SHOWS PRESSURES FOR A NEW REPLACEMENT DOOR/SIDELITE AND
 (2) WINDOWS. BOTH ARE INDICATED AS DESIGN PRESSURES BUT
 THE DOOR AND SIDELITE APPEAR TO BE VULT PRESSURES
 -70.84. 2014 FBC-B TABLE 1609.6.2.
  
 2) THERE IS STILL (2) ISSUES, THE FLORIDA COVERSHEET
 FOR THE PGT PRODUCTS WAS NOT SUBMITTED, THE SECOND
 ISSUE IS COMPLIANCE WITH THE 2014 FLORIDA BUILDING CODE
 W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.4.1
 THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. NONE OF THE (3) PRODUCT
 APPROVALS HAVE BEEN REVIEWED BY THE DESIGNER OF RECORD
 FOR THE JOB.
 ORIGINAL COMMENT # 2. THE 2 SUBMITTED REPORTS FROM
 KEYSTONE AND PGT DO NOT HAVE IDENTIFICATION AS TO IF
 THESE REPORTS ARE FLORIDA APPROVALS OR IF THEY ARE A
 MIAMI-DADE NOA, PLEASE PROVIDE THE COVERSHEETS
 IDENTIFYING THE SOURCE OF EACH OF THESE REPORTS. 2014
 FBC-B 16-0.1.2 PROTECTION OF OPENINGS.
  
 3) COMPLIED. SHEET A4 SECTION # 1 METAL CANOPY FRAMING
 DOES NOT INDICATE THE FRAMING MATERIAL, SIZE OF FRAMING
 MEMBER, CENTER TO CENTER OF FRAMING MEMBERS, LOADS THEY
 CAN CARRY, IF STIFF BACKS ARE REQUIRED, BRACING, NOR
 DOES THE PLANS SHOW THE TYPE OF ROOF SHEATHING,
 THICKNESS, FACIA, SOFFIT MATERIAL IS NOT IDENTIFIED,
 THE TOP OF THE PARAPET AND NEW MANSARD ROOF FRAMING
 DOES NOT PROVIDE WHAT TYPE OF COPYING DETAIL WILL BE
 USED IN THIS INSTALLATION. 107.3.5.1 MINIMUM PLAN
 REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. A THOROUGH
 REVIEW CANNOT BE MADE AT THIS TIME, AS A RESULT OF THE
 ADDITIONAL INFORMATION REQUESTED ADDITIONAL COMMENTS
 MAY APPEAR THAT WERE NOT PART OF THIS REVIEW.
  
 4) SEMI-COMPLIED. THE ROOFING PRODUCT APPROVAL WAS
 SUBMITTED, THE CONTRACTOR NOR THE DESIGNER OF RECORD
 HAS IDENTIFIED THE ROOFING SUB-SYSTEM TO BE INSTALLED
 AND THE ASSOCIATED PRESSURES, SEE MAXIMUM DESIGN
 PRESSURES AND LIMITATIONS, EITHER 7 OR 9. 107.3.4.1
 THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
  
 THE SUBMITTED A/C ALUMINUM ROOF STAND PLEASE HAVE THE
 DESIGNER OF RECORD REVIEW AND APPROVE THE PRODUCT
 APPROVAL AND APPLY THEIR SHOP DRAWING STAMP OF
 APPROVAL. 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 ORIGINAL COMMENT # 4.THIS REVIEW CYCLE NO ROOFING
 PRODUCT APPROVALS WERE SUBMITTED. PLEASE PROVIDE
 COMPLIANCE WITH: 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED ROOFTOP A/C STANDS
  
 5) 2ND REQUEST. COMMENT NOT RESPONDED TOO, THE ORIGINAL
 M1SHEET LEFT IN THE OLD SET OF PLANS. SHEET M1 SHOWS A
 DETAIL FOR A ROOF TOP A/C CONDENSING STAND. PLEASE NOTE
 THE STAND WILL REQUIRE A PRODUCT APPROVAL TO BE
 SUBMITTED FOR REVIEW. PLEASE NOTE ADDITIONAL
 INFORMATION WILL BE REQUIRED AS TO THE TYPE OF ROOF
 DECK IS ON THE EXISTING BUILDING. SHEET A4 THE BUILDING
 SECTION IT APPEARS THE ROOF DECK IS WOOD WITH WOOD
 CEILING JOIST/ RAFTERS WHERE AS THE MECHANICAL PLAN M1
 THE ROOF DECK IS A CONCRETE DECK. DISCREPANCY IN PLANS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) 2ND RESPONSE, NOT RESPONDED TOO. PLEASE NOTE THE
 PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE INDICATES
 FOR 2015 THE IMPROVEMENT VALUE OF THE BUILDING IS
 $42,253 DOLLARS IN VALUE.
 CHAPTER 2 DEFINITIONS (C) RENOVATED BUILDING. A
 RESIDENTIAL OR NONRESIDENTIAL BUILDING UNDERGOING
 ALTERATION THAT VARIES OR CHANGES INSULATION, HVAC
 SYSTEMS, WATER HEATING SYSTEMS, OR EXTERIOR ENVELOPE
 CONDITIONS, PROVIDED THE ESTIMATED COST OF RENOVATION
 EXCEEDS 30 PERCENT OF THE ASSESSED VALUE OF THE
 STRUCTURE.
  
  
 2014 FBC-ENERGY CODE C101.5 COMPLIANCE. COMMERCIAL
 BUILDINGS SHALL MEET THE COMMERCIAL PROVISIONS.
  
 C101.5.1 COMPLIANCE MATERIALS. THE FLORIDA BUILDING
 COMMISSION SHALL APPROVE SPECIFIC COMPUTER SOFTWARE.
 THE CODE OFFICIAL SHALL BE PERMITTED TO APPROVE
 WORKSHEETS, COMPLIANCE MANUALS AND OTHER SIMILAR
 MATERIALS THAT MEET THE INTENT OF THIS CODE.
  
 C101.5.1.1 ALTERATIONS, RENOVATIONS AND BUILDING
 SYSTEMS. ALTERATIONS, RENOVATIONS AND BUILDING SYSTEMS
 MAY UTILIZE FORM C402. FORM C402 CAN BE FOUND IN
 APPENDIX C.
  
  
 C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL COMPLY
 WITH ONE OF THE FOLLOWING:
 C401.2.1 APPLICATION TO EXISTING BUILDINGS.
 ADDITIONS, ALTERATIONS AND REPAIRS TO EXISTING
 BUILDINGS SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. SECTIONS C402, C403, C404 AND C405; OR
 2. ANSI/ASHRAE/IESNA 90.1.
  
 7) NEW COMMENT. MISSING A1 SHEET LEFT IN THE OLD SET OF
 PLANS.
  
 8) ALL SHEETS SIGNED AND SEALED BY JOHN P. STOPPI JR.
 P.E. 78807 ARE PHOTOCOPIED SIGNATURES NOT ORIGINAL
 SIGNATURE.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 EFFECTIVE DATE 05/06/2009
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  