| 2016-01-20 07:52:05 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15100707 |
| | ADD: 831 BELVEDERE RD. |
| | CONT: AJS BUILDING & RENOVATIONS, INC. |
| | TEL: (407)298-9700 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. JAN. 20/2016 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST. RESPONSE INDICATES THE DESIGN PRESSURES |
| | FOR NEW WINDOWS AND DOORS THE CALCULATIONS ARE |
| | ATTACHED. THE WIND DESIGN CRITERIA AND ASSOCIATED |
| | PRESSURES ARE CORRECT. THE WIND DESIGN CRITERIA AND |
| | PRESSURES ARE FROM VVS ENGINEERING; THEY ARE NOT SIGNED |
| | NOR SEALED. . PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING |
| | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| | DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | EFFECTIVE DATE 05/06/2009 |
| | |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. THE ENGINEER OF RECORD |
| | JOHN STOPPI P. E. SHOULD APPLY HIS SHOP DRAWING STAMP |
| | REVIEWED AND APPROVED. |
| | |
| | |
| | ORIGINAL COMMENT # 1. SHEET A4 BUILDING EAST ELEVATION |
| | SHOWS PRESSURES FOR A NEW REPLACEMENT DOOR/SIDELITE AND |
| | (2) WINDOWS. BOTH ARE INDICATED AS DESIGN PRESSURES BUT |
| | THE DOOR AND SIDELITE APPEAR TO BE VULT PRESSURES |
| | -70.84. 2014 FBC-B TABLE 1609.6.2. |
| | |
| | 2) THERE IS STILL (2) ISSUES, THE FLORIDA COVERSHEET |
| | FOR THE PGT PRODUCTS WAS NOT SUBMITTED, THE SECOND |
| | ISSUE IS COMPLIANCE WITH THE 2014 FLORIDA BUILDING CODE |
| | W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.4.1 |
| | THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. NONE OF THE (3) PRODUCT |
| | APPROVALS HAVE BEEN REVIEWED BY THE DESIGNER OF RECORD |
| | FOR THE JOB. |
| | ORIGINAL COMMENT # 2. THE 2 SUBMITTED REPORTS FROM |
| | KEYSTONE AND PGT DO NOT HAVE IDENTIFICATION AS TO IF |
| | THESE REPORTS ARE FLORIDA APPROVALS OR IF THEY ARE A |
| | MIAMI-DADE NOA, PLEASE PROVIDE THE COVERSHEETS |
| | IDENTIFYING THE SOURCE OF EACH OF THESE REPORTS. 2014 |
| | FBC-B 16-0.1.2 PROTECTION OF OPENINGS. |
| | |
| | 3) COMPLIED. SHEET A4 SECTION # 1 METAL CANOPY FRAMING |
| | DOES NOT INDICATE THE FRAMING MATERIAL, SIZE OF FRAMING |
| | MEMBER, CENTER TO CENTER OF FRAMING MEMBERS, LOADS THEY |
| | CAN CARRY, IF STIFF BACKS ARE REQUIRED, BRACING, NOR |
| | DOES THE PLANS SHOW THE TYPE OF ROOF SHEATHING, |
| | THICKNESS, FACIA, SOFFIT MATERIAL IS NOT IDENTIFIED, |
| | THE TOP OF THE PARAPET AND NEW MANSARD ROOF FRAMING |
| | DOES NOT PROVIDE WHAT TYPE OF COPYING DETAIL WILL BE |
| | USED IN THIS INSTALLATION. 107.3.5.1 MINIMUM PLAN |
| | REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. A THOROUGH |
| | REVIEW CANNOT BE MADE AT THIS TIME, AS A RESULT OF THE |
| | ADDITIONAL INFORMATION REQUESTED ADDITIONAL COMMENTS |
| | MAY APPEAR THAT WERE NOT PART OF THIS REVIEW. |
| | |
| | 4) SEMI-COMPLIED. THE ROOFING PRODUCT APPROVAL WAS |
| | SUBMITTED, THE CONTRACTOR NOR THE DESIGNER OF RECORD |
| | HAS IDENTIFIED THE ROOFING SUB-SYSTEM TO BE INSTALLED |
| | AND THE ASSOCIATED PRESSURES, SEE MAXIMUM DESIGN |
| | PRESSURES AND LIMITATIONS, EITHER 7 OR 9. 107.3.4.1 |
| | THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | |
| | THE SUBMITTED A/C ALUMINUM ROOF STAND PLEASE HAVE THE |
| | DESIGNER OF RECORD REVIEW AND APPROVE THE PRODUCT |
| | APPROVAL AND APPLY THEIR SHOP DRAWING STAMP OF |
| | APPROVAL. 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED |
| | BY DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | ORIGINAL COMMENT # 4.THIS REVIEW CYCLE NO ROOFING |
| | PRODUCT APPROVALS WERE SUBMITTED. PLEASE PROVIDE |
| | COMPLIANCE WITH: 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31) (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (G) PRE-ENGINEERED ROOFTOP A/C STANDS |
| | |
| | 5) 2ND REQUEST. COMMENT NOT RESPONDED TOO, THE ORIGINAL |
| | M1SHEET LEFT IN THE OLD SET OF PLANS. SHEET M1 SHOWS A |
| | DETAIL FOR A ROOF TOP A/C CONDENSING STAND. PLEASE NOTE |
| | THE STAND WILL REQUIRE A PRODUCT APPROVAL TO BE |
| | SUBMITTED FOR REVIEW. PLEASE NOTE ADDITIONAL |
| | INFORMATION WILL BE REQUIRED AS TO THE TYPE OF ROOF |
| | DECK IS ON THE EXISTING BUILDING. SHEET A4 THE BUILDING |
| | SECTION IT APPEARS THE ROOF DECK IS WOOD WITH WOOD |
| | CEILING JOIST/ RAFTERS WHERE AS THE MECHANICAL PLAN M1 |
| | THE ROOF DECK IS A CONCRETE DECK. DISCREPANCY IN PLANS. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 6) 2ND RESPONSE, NOT RESPONDED TOO. PLEASE NOTE THE |
| | PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE INDICATES |
| | FOR 2015 THE IMPROVEMENT VALUE OF THE BUILDING IS |
| | $42,253 DOLLARS IN VALUE. |
| | CHAPTER 2 DEFINITIONS (C) RENOVATED BUILDING. A |
| | RESIDENTIAL OR NONRESIDENTIAL BUILDING UNDERGOING |
| | ALTERATION THAT VARIES OR CHANGES INSULATION, HVAC |
| | SYSTEMS, WATER HEATING SYSTEMS, OR EXTERIOR ENVELOPE |
| | CONDITIONS, PROVIDED THE ESTIMATED COST OF RENOVATION |
| | EXCEEDS 30 PERCENT OF THE ASSESSED VALUE OF THE |
| | STRUCTURE. |
| | |
| | |
| | 2014 FBC-ENERGY CODE C101.5 COMPLIANCE. COMMERCIAL |
| | BUILDINGS SHALL MEET THE COMMERCIAL PROVISIONS. |
| | |
| | C101.5.1 COMPLIANCE MATERIALS. THE FLORIDA BUILDING |
| | COMMISSION SHALL APPROVE SPECIFIC COMPUTER SOFTWARE. |
| | THE CODE OFFICIAL SHALL BE PERMITTED TO APPROVE |
| | WORKSHEETS, COMPLIANCE MANUALS AND OTHER SIMILAR |
| | MATERIALS THAT MEET THE INTENT OF THIS CODE. |
| | |
| | C101.5.1.1 ALTERATIONS, RENOVATIONS AND BUILDING |
| | SYSTEMS. ALTERATIONS, RENOVATIONS AND BUILDING SYSTEMS |
| | MAY UTILIZE FORM C402. FORM C402 CAN BE FOUND IN |
| | APPENDIX C. |
| | |
| | |
| | C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL COMPLY |
| | WITH ONE OF THE FOLLOWING: |
| | C401.2.1 APPLICATION TO EXISTING BUILDINGS. |
| | ADDITIONS, ALTERATIONS AND REPAIRS TO EXISTING |
| | BUILDINGS SHALL COMPLY WITH ONE OF THE FOLLOWING: |
| | 1. SECTIONS C402, C403, C404 AND C405; OR |
| | 2. ANSI/ASHRAE/IESNA 90.1. |
| | |
| | 7) NEW COMMENT. MISSING A1 SHEET LEFT IN THE OLD SET OF |
| | PLANS. |
| | |
| | 8) ALL SHEETS SIGNED AND SEALED BY JOHN P. STOPPI JR. |
| | P.E. 78807 ARE PHOTOCOPIED SIGNATURES NOT ORIGINAL |
| | SIGNATURE. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | EFFECTIVE DATE 05/06/2009 |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |