| Plan Review Notes For Permit 15100707 |
| Permit Number |
15100707 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-03 15:53:32 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15100707 | | | 11/3/15 | | | | | | 1) THE PROPOSED PROJECT IS CLASSIFIED AS A RENOVATED | | | BUILDING IN ACCORDANCE WITH SECTION C202 FBC-14 ENERGY | | | CONSERVATION, AND THEREFORE SHALL BE IN COMPLIANCE WITH | | | THE CURRENT CODE PER SECTION C101.4.3. PLEASE SUBMIT | | | TWO COPIES OF COMPLIANCE DOCUMENTATION USING EITHER THE | | | PRESCRIPTIVE OR PERFORMANCE BASED COMPLIANCE PATH AS | | | OUTLINED IN SECTION C101.5.1. | | | 2) REFER TO SECTION C403.2.1 AND SUBMIT COOLING AND | | | HEATING CALCULATIONS FOR THE NEW 3-TON AC SYSTEM IN | | | ACCORDANCE WITH THE PROCEDURES DESRIBED IN THE | | | ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL N. | | | 3) THE CORRIDOR CANNOT BE USED TO CONVEY RETURN AIR | | | FROM THE OFFICES PER SECTION 601.2 FBC-14 MECHANICAL. | | | 4) SITE SPECIFIC WINDLOAD ENGINEERING IS REQUIRED FOR | | | ROOFTOP AC UNITS IN COMPLIANCE WITH SECTION 301.15. THE | | | ENGINEER OF RECORD MUST PROVIDE THE WIND LOAD DESIGN | | | CRITERIA AND DESIGN PRESSURES ON THE PLAN, AND SUBMIT | | | REVIEWED AND APPROVED NOA'S OR PRODUCT APPROVALS FOR | | | THE ROOF STAND AND CLIPS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|