2015-11-03 15:53:321ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100707
 11/3/15
  
 1) THE PROPOSED PROJECT IS CLASSIFIED AS A RENOVATED
 BUILDING IN ACCORDANCE WITH SECTION C202 FBC-14 ENERGY
 CONSERVATION, AND THEREFORE SHALL BE IN COMPLIANCE WITH
 THE CURRENT CODE PER SECTION C101.4.3. PLEASE SUBMIT
 TWO COPIES OF COMPLIANCE DOCUMENTATION USING EITHER THE
 PRESCRIPTIVE OR PERFORMANCE BASED COMPLIANCE PATH AS
 OUTLINED IN SECTION C101.5.1.
 2) REFER TO SECTION C403.2.1 AND SUBMIT COOLING AND
 HEATING CALCULATIONS FOR THE NEW 3-TON AC SYSTEM IN
 ACCORDANCE WITH THE PROCEDURES DESRIBED IN THE
 ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL N.
 3) THE CORRIDOR CANNOT BE USED TO CONVEY RETURN AIR
 FROM THE OFFICES PER SECTION 601.2 FBC-14 MECHANICAL.
 4) SITE SPECIFIC WINDLOAD ENGINEERING IS REQUIRED FOR
 ROOFTOP AC UNITS IN COMPLIANCE WITH SECTION 301.15. THE
 ENGINEER OF RECORD MUST PROVIDE THE WIND LOAD DESIGN
 CRITERIA AND DESIGN PRESSURES ON THE PLAN, AND SUBMIT
 REVIEWED AND APPROVED NOA'S OR PRODUCT APPROVALS FOR
 THE ROOF STAND AND CLIPS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719