| 2015-11-04 09:21:57 | 831 BELVEDERE ROAD | | | PERMIT #15100707 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE SMALLER STORAGE ROOM ON THE EAST SIDE OF THE | | | BUILDING HAS AN NON-FIRE RATED OVERHEAD DOOR LOCATED | | | WITHIN 10 FEET OF THE BUSINESS OCCUPANCY EXIT DOOR. PER | | | SECTION 8.7, ANY AREA (STORAGE) HAVING A DEGREE OF | | | HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY | | | (BUSINESS) OF THE BUILDING, SHALL BE SEPARATED FROM | | | ADJACENT AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR BE | | | PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS | | | SHALL BE SELF CLOSING, POSITIVE LATCHING, AND | | | FIRE-RATED FOR AT LEAST 45-MINUTES. | | | | | | PLANS DO NOT INDICATE ANY EXISTING LIGHTING OR PORTABLE | | | FIRE EXTINGUISHERS IN THE SMALL STORAGE ROOM ON THE | | | EAST SIDE OF THE BUILDING. | | | | | | PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE | | | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING | | | FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE | | | AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. | | | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON | | | CENTER. | | | | | | PER SECTION 8.3.5.1, PENETRATIONS THROUGH A FIRE-RATED | | | WALL ASSEMBLY SHALL BE PROTECTED BY A FIRESTOP SYSTEM | | | OR DEVICE. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|