2015-11-04 09:21:57831 BELVEDERE ROAD
 PERMIT #15100707
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE SMALLER STORAGE ROOM ON THE EAST SIDE OF THE
 BUILDING HAS AN NON-FIRE RATED OVERHEAD DOOR LOCATED
 WITHIN 10 FEET OF THE BUSINESS OCCUPANCY EXIT DOOR. PER
 SECTION 8.7, ANY AREA (STORAGE) HAVING A DEGREE OF
 HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY
 (BUSINESS) OF THE BUILDING, SHALL BE SEPARATED FROM
 ADJACENT AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR BE
 PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS
 SHALL BE SELF CLOSING, POSITIVE LATCHING, AND
 FIRE-RATED FOR AT LEAST 45-MINUTES.
  
 PLANS DO NOT INDICATE ANY EXISTING LIGHTING OR PORTABLE
 FIRE EXTINGUISHERS IN THE SMALL STORAGE ROOM ON THE
 EAST SIDE OF THE BUILDING.
  
 PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE
 AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 PER SECTION 8.3.5.1, PENETRATIONS THROUGH A FIRE-RATED
 WALL ASSEMBLY SHALL BE PROTECTED BY A FIRESTOP SYSTEM
 OR DEVICE.
  