| 2015-11-06 08:41:32 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15100707 |
| | ADD: 831 BELVEDERE RD. |
| | CONT: AJS BUILDING & RENOVATIONS, INC. |
| | TEL: (407)298-9700 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. NOV. 06/2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A4 BUILDING EAST ELEVATION SHOWS PRESSURES FOR |
| | A NEW REPLACEMENT DOOR/SIDELITE AND (2) WINDOWS. BOTH |
| | ARE INDICATED AS DESIGN PRESSURES BUT THE DOOR AND |
| | SIDELITE APPEAR TO BE VULT PRESSURES -70.84. 2014 FBC-B |
| | TABLE 1609.6.2. |
| | |
| | 2) THE 2 SUBMITED REPORTS FROM KEYSTONE AND PGT DO NOT |
| | HAVE IDENTIFICATION AS TO IF THESE REPORTS ARE FLORIDA |
| | APPROVALS OR IF THEY ARE A MIAMI-DADE NOA, PLEASE |
| | PROVIDE THE COVERSHEETS IDENTIFYING THE SOURCE OF EACH |
| | OF THESE REPORTS. 2014 FBC-B 16-0.1.2 PROTECTION OF |
| | OPENINGS. |
| | |
| | 3) SHEET A4 SECTION # 1 METAL CANOPY FRAMING DOES NOT |
| | INDICATE THE FRAMING MATERIAL, SIZE OF FRAMING MEMBER, |
| | CENTER TO CENTER OF FRAMING MEMBERS, LOADS THEY CAN |
| | CARRY, IF STIFFBACKS ARE REQUIRED, BRACING, NOR DOES |
| | THE PLANS SHOW THE TYPE OF ROOF SHEATHING, THICKNESS, |
| | FACIA, SOFFIT MATERIAL IS NOT IDENTIFIED, THE TOP OF |
| | THE PARAPET AND NEW MANSARD ROOF FRAMING DOES NOT |
| | PROVIDE WHAT TYPE OF COPYING DETAIL WILL BE USED IN |
| | THIS INSTALATION. 107.3.5.1 MINIMUM PLAN REVIEW |
| | CRITERIA FOR COMMERCIAL BUILDINGS. A THOROUGH REVIEW |
| | CANNOT BE MADE AT THIS TIME, AS A RESULT OF THE |
| | ADDITIONAL INFORMATION REQUESTED ADDITIONAL COMMENTS |
| | MAY APPEAR THAT WERE NOT PART OF THIS REVIEW. |
| | |
| | 4) THIS REVIEW CYCLE NO ROOFING PRODUCT APPROVALS WERE |
| | SUBMITTED. PLEASE PROVIDE COMPLIANCE WITH: 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31) (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (G) PRE-ENGINEERED ROOFTOP A/C STANDS |
| | |
| | 5) SHEET M1 SHOWS A DETAIL FOR A ROOF TOP A/C |
| | CONDENSING STAND. PLEASE NOTE THE STAND WILL REQUIRE A |
| | PRODUCT APPROVAL TO BE SUBMITTED FOR REVIEW. PLEASE |
| | NOTE ADDITIONAL INFORMATION WILL BW REQUIRED AS TO THE |
| | TYPE OF ROOF DECK IS ON THE EXISITNG BUILDING. SHEET A4 |
| | THE BUILDING SECTION IT APPEARS THE ROOF DECK IS WOOD |
| | WITH WOOD CEILING JOIST/ RAFTERS WHERE AS THE |
| | MECHANICAL PLAN M1 THE ROOF DECK IS A CONCRETE DECK. |
| | DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 6) PLEASE NOTE THE PALM BEACH COUNTY PROPERTY |
| | APPRAISERS OFFICE INDICATES FOR 2015 THE IMPROVEMENT |
| | VALUE OF THE BUILDING IS $42,253 DOLLARS IN VALUE. |
| | CHAPTER 2 DEFINITIONS (C) RENOVATED BUILDING. A |
| | RESIDENTIAL OR NONRESIDENTIAL BUILDING UNDERGOING |
| | ALTERATION THAT VARIES OR CHANGES INSULATION, HVAC |
| | SYSTEMS, WATER HEATING SYSTEMS, OR EXTERIOR ENVELOPE |
| | CONDITIONS, PROVIDED THE ESTIMATED COST OF RENOVATION |
| | EXCEEDS 30 PERCENT OF THE ASSESSED VALUE OF THE |
| | STRUCTURE. |
| | |
| | |
| | 2014 FBC-ENERGY CODE C101.5 COMPLIANCE. COMMERCIAL |
| | BUILDINGS SHALL MEET THE COMMERCIAL PROVISIONS. |
| | |
| | C101.5.1 COMPLIANCE MATERIALS. THE FLORIDA BUILDING |
| | COMMISSION SHALL APPROVE SPECIFIC COMPUTER SOFTWARE. |
| | THE CODE OFFICIAL SHALL BE PERMITTED TO APPROVE |
| | WORKSHEETS, COMPLIANCE MANUALS AND OTHER SIMILAR |
| | MATERIALS THAT MEET THE INTENT OF THIS CODE. |
| | |
| | C101.5.1.1 ALTERATIONS, RENOVATIONS AND BUILDING |
| | SYSTEMS. ALTERATIONS, RENOVATIONS AND BUILDING SYSTEMS |
| | MAY UTILIZE FORM C402. FORM C402 CAN BE FOUND IN |
| | APPENDIX C. |
| | |
| | |
| | C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL COMPLY |
| | WITH ONE OF THE FOLLOWING: |
| | C401.2.1 APPLICATION TO EXISTING BUILDINGS. |
| | ADDITIONS, ALTERATIONS AND REPAIRS TO EXISTING |
| | BUILDINGS SHALL COMPLY WITH ONE OF THE FOLLOWING: |
| | 1. SECTIONS C402, C403, C404 AND C405; OR |
| | 2. ANSI/ASHRAE/IESNA 90.1. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |