| Plan Review Notes For Permit 15100683 |
| Permit Number |
15100683 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-01-07 15:29:28 | FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | MIKE ALBARRAN | | | 561-805-6746 | | | [email protected] | | | | | | | | | PROVISO: C405.2.4 EXTERIOR LIGHTING CONTROLS. | | | LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY EITHER A COMBINATION OF A | | | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME | | | SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF | | | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS | | | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. | | | | | | |
|