| Plan Review Notes For Permit 15100682 |
| Permit Number |
15100682 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-01-05 10:15:25 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15100682 | | | 01/05/16 | | | | | | 1) SHEET M-1: THE LOCATION OF THE OUTDOOR AIR INTAKE ON | | | THE WEST SIDE OF THE FIRST FLOOR APPEARS TO BE NOT IN | | | COMPLIANCE WITH SECTION 401.4 ITEM #2 WHIC REQUIRES A | | | 10' CLEARANCE TO THE PARKING LOT OR DRIVE LANE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|