2016-01-14 09:02:54YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED
 DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL
 REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED
 BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO
 SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE
 REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION
 OF ANY PREVIOUS COMMENTS.
 ALL OF THE PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED EXCEPT THE ONE MENTIONED
 BELOW.
 COMMENT #2: NEC 215.5 REQUIRES A FEEDER DIAGRAM WITH
 LOAD CALCS AND CONDUCTOR SIZING. THE FEEDER DIAGRAM
 PROVIDED FAILS TO INCLUDE ALL THE PANELS INCLUDED
 WITHIN THE AREA OF THE SCOPE OF WORK.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER