| 2015-11-04 08:08:32 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15100682 |
| | 11/4/2015 |
| | |
| | 1) SHEET D-2.0: THE DEMO NOTES SHOWN ON THE 2ND FLOOR |
| | RCP DO NOT MAKE SENSE WITH THE DRAWING: PLEASE REVISE. |
| | 2) M-1: THE PLANS ARE VERY VAGUE AND SHOW ONLY TWO DUCT |
| | RELOCATIONS IN THE EXPANDED IT ROOM. PLEASE SHOW ALL |
| | RELOCATED DUCTS, DIIFFUSERS, AND RETURN GRILLS ON THE |
| | PLAN BASED ON THE NEW CEILING AND LIGHTING LAYOUTS, |
| | INCLUDING THE WAREHOUSE WHERE THE SUSPENDED CEILING |
| | WILL BE REMOVED ENTIRELY. |
| | 3) PROVIDE AN AIR DEVICE SCHEDULE. |
| | 4) REFER TO SECTION 809.2 FBC-14 EXISTING BUIILDING |
| | CODE- ALTERED EXISTING SYSTEMS. |
| | IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL |
| | VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR |
| | EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER |
| | MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR |
| | AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION |
| | AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF |
| | VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY |
| | PROCEDURE OF ASHRAE 62. PLEASE PROVIDE CALCULATIONS ON |
| | THE PLAN TO INDICATE COMPLIANCE. |
| | 5) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH |
| | SECTION C101.4.3 FBC-14 ENERGY CONSERVATION. |
| | |