Plan Review Notes
Plan Review Notes For Permit 15100682
Permit Number 15100682
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-10-29 09:54:53THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1. SHEET A 0.0, INDICATES AN INCORRECT REFERENCE TO THE
 FIRE CODE,
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
  
 2. SHEET E 1, DOES NOT INDICATE AN EXIT SIGN AT THE NEW
 DOOR FROM THE CORRIDOR TO THE IT ROOM. INSTALL AN EXIT
 SIGN INSIDE THE CORRIDOR AT THE IT ROOM DOOR.
  
 3. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 ANY FIRE ALARM SYSTEM EQUIPMENT FOR CODE COVERAGE AND
 COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS
 REQUIRE AN EVALUATION OF THE EXISTING EQUIPMENT.
 IF EXISTING, THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEM, EXCEEDS 4
 HOURS, A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED
 UNTIL FULL AND COMPLETE PROTECTION IS RETURNED.
  
  