| 2015-10-29 09:54:53 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | 1. SHEET A 0.0, INDICATES AN INCORRECT REFERENCE TO THE |
| | FIRE CODE, |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | |
| | 2. SHEET E 1, DOES NOT INDICATE AN EXIT SIGN AT THE NEW |
| | DOOR FROM THE CORRIDOR TO THE IT ROOM. INSTALL AN EXIT |
| | SIGN INSIDE THE CORRIDOR AT THE IT ROOM DOOR. |
| | |
| | 3. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF |
| | ANY FIRE ALARM SYSTEM EQUIPMENT FOR CODE COVERAGE AND |
| | COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS |
| | REQUIRE AN EVALUATION OF THE EXISTING EQUIPMENT. |
| | IF EXISTING, THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE |
| | THROUGHOUT THE CONSTRUCTION PERIOD. |
| | ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE |
| | UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE |
| | SAFETY CONTRACTORS. |
| | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEM, EXCEEDS 4 |
| | HOURS, A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED |
| | UNTIL FULL AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | |