Plan Review Notes
Plan Review Notes For Permit 15100682
Permit Number 15100682
Review Stop B
Sequence Number 1
Notes
Date Text
2015-11-03 12:31:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100682
 ADD: 5827 CORPORATE WAY
 CONT: SHIFF
 TEL: (954)524-2575
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JAN. 08/2016
 ACTION: DENIED
  
 1-5) COMPLIED.
  
 6) 2ND REQUEST. RESPONSE INDICATES PLEASE SEE ENCLOSED
 FIRE ALARM SHOP DRAWINGS. THE COVERSHEET A-0.0
 INDICATES THE OCCUPANT LOAD OF ON BOTH THE 1ST FLOOR
 AND 2ND FLOOR AS 90+ WHEREAS THE SQUARE FOOTAGE IS
 10,040 SQ. FT./ 100= 101 OCCUPANTS. THE 2014 EXISTING
 BUILDING CODE 904.2.1 WILL REFER YOU FOR A MANUAL FIRE
 ALARM TO THE FBC-BUILDING 907.2.2 SINCE THE BUSINESS
 OCCUPANCY ON THE 2 ND FLOOR IS OVER 100 IN GROUP B
 OCCUPANCY.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  