| Plan Review Notes For Permit 15100677 |
| Permit Number |
15100677 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-17 13:32:57 | FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | -PROVIDE VOLTAGE DROP CALCULATIONS FROM PANELBOARD | | | LOCATION TO LAST SITE LIGHTING ON THE PARTICULAR | | | CIRCUIT.FBC-E C405.7.3.1 FEEDERS AND CUSTOMER OWNED | | | SERVICE CONDUCTORS. | | | SHALL BE SIZED FOR A MAXIMUM VOLTAGE DROP OF 2 PERCENT | | | AT DESIGN LOAD AND 3 % FOR BRANCH CIRCUITS. | | | | | | ( THIS WILL SHOW US IF ADEQUATE PROTECTION AND WIRE | | | SIZES ARE CORRECT AS PER PLAN. ) PANEL C SHOWS ON THE | | | 4TH FLOOR ACCORDING TO RISER DIAGRAM. | | | |
|