2016-02-17 13:32:57FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 -PROVIDE VOLTAGE DROP CALCULATIONS FROM PANELBOARD
 LOCATION TO LAST SITE LIGHTING ON THE PARTICULAR
 CIRCUIT.FBC-E C405.7.3.1 FEEDERS AND CUSTOMER OWNED
 SERVICE CONDUCTORS.
 SHALL BE SIZED FOR A MAXIMUM VOLTAGE DROP OF 2 PERCENT
 AT DESIGN LOAD AND 3 % FOR BRANCH CIRCUITS.
  
 ( THIS WILL SHOW US IF ADEQUATE PROTECTION AND WIRE
 SIZES ARE CORRECT AS PER PLAN. ) PANEL C SHOWS ON THE
 4TH FLOOR ACCORDING TO RISER DIAGRAM.
  