| 2015-11-18 14:30:35 | 1ST REVIEW: FBC 2014 RESIDENTIAL | | | PERMIT #15100627 | | | 11/18/15 | | | | | | 1) THE MANUAL J WORKSHEETS INDICATE 195 CFM'S OF | | | COOLING AND 224 CFM'S OF HEATING ARE REQUIRED FOR THE | | | DEN. PLEASE CLARIFY HOW SUPPLY AIR AND RETURN AIR ARE | | | BEING PROVIDED TO AND FROM THE ROOM- WILL THERE BE TWO | | | TRANSFER GRILLS? | | | 2) REFER TO SECTION M1305.1.3 FBC-14 RESIDENTIAL | | | ANDR403.2.4 FBC-14 ENERGY CONSERVATION AND PROVIDE THE | | | DIMENSIONS OF THE ATTIC ACCESS, AND CONSTRUCTION | | | DETAILS AND NOTES INDICATING COMPLIANCE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|