2015-10-26 13:28:19THE SUBMITTED DRAWINGS HAVE A LOT OF ELECTRICAL
 INFORMATION, BUT I NEED FOR THE ELECTRICAL CONTRACTOR
 TO PROVIDE A WIRING SCHEMATIC AND FEEDER SCHEDULE
 INDICATING LOCATION OF SOURCE PANEL AND WIRING METHODS
 TO EACH UNIT. THIS SCHEMATIC SHALL INCLUDE CONDUCTOR
 SIZING AND OCP.