Plan Review Notes
Plan Review Notes For Permit 15100614
Permit Number 15100614
Review Stop P
Sequence Number 1
Notes
Date Text
2015-10-23 07:40:121) SHT.3-FLOW RATE CALCS- THE MINIMUM FILTER AREA IS
 SHOWN AS 200 X 0.375=56 GPM. ACTUALLY 200 X 0.375 = 75.
 CLARIFY.
 2) SHT. 3 - MIDDLE OF PAGE - "PER ANSI -7" - THE TEXT
 STATES MINIMUM SIZES BUT PIPE VELOCITIES ARE CALLED
 OUT, NOT THE PIPE SIZES. CLARIFY.
 3) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS FOR
 THE SALT GENERATOR. WPB AMEND. TO FBC SEC. 107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  