| Plan Review Notes For Permit 15100606 |
| Permit Number |
15100606 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-03-23 19:43:04 | PASSED ELECTRICAL REVIEW BUT MADE SEVERAL NOTES ON THE | | | PLANS FOR FINAL INSPECTIONS. | | | 1. REVISED THE QUOTED EDITION OF THE NEC TO 2011 | | | 2. MARKED FACP CKT ON BOTH PANEL SCHEDULE AND FIRE | | | ALARM RISER TO REFERENCE NEC 760.121 (B) INDICATING THE | | | BRANCH CIRCUIT REQUIREMENTS. | | | 3. MARKED THE PANEL SCHEDULE TO NOTE THAT THE EWC SHALL | | | BE PROTECTED BY GFCI AS PER NEC 422.52 | | | | | | |
|