| 2015-10-30 14:49:16 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15100606 |
| | ADD: 6501 N. JOG RD. |
| | CONT: ANDREA CONSTRUCTION, INC. |
| | TEL: (561)358-4797 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. OCT. 30/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET INDICATES IN THE NOTES THE STRUCTURAL |
| | MODIFICATIONS HAVE BEEN DESIGNED IN ACCORDANCE WITH THE |
| | 2010 FBC. PLEASE BE AWARE THAT THE 2014 FBC, THE 5TH |
| | EDITION OF THE FLORIDA BUILDING CODE WENT INTO AFFECT |
| | STATEWIDE JUNE 30/ 2015. |
| | |
| | 2) THE COVERSHEET ALSO INDICATES AS DEFINED BY THE 2014 |
| | FBC-EXISITNG BUILDING CODE THIS IS TO BE A LEVEL 3 |
| | ALTERATION. PLEASE SHOW COMPLIANCE WITH: |
| | 2014 EXIST. BLDG CODE 907.4.1 EVALUATION AND ANALYSIS. |
| | AN ENGINEERING EVALUATION AND ANALYSIS THAT ESTABLISHES |
| | THE STRUCTURAL ADEQUACY OF THE ALTERED STRUCTURE SHALL |
| | BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL AND |
| | SUBMITTED TO THE CODE OFFICIAL. |
| | |
| | 3) THE COVERSHEET DOESN'T DECLARE IF THIS IS A LIMITED |
| | STRUCTURAL ALTERATION(B)907.4.3 OR SUBSTANTIAL |
| | STRUCTURAL ALTERATION (B) 907.2 SUBSSTANTIAL STRUCTURAL |
| | ALTERATION. |
| | |
| | 4) SHEET A1.1 & A1.2 SHOW THE WORK TO BE PREFORMED BUT |
| | THERE ARE NOTES THAT NO NEW WORK IN THE RESTROOMS NOR |
| | THE BREAK AREA. THE CONTRACT VALUE IS $84500.00. 20% |
| | OF THAT DOLLAR VALUE IS $16,900.00. THE 2014 |
| | FBC-ACCESSIBILITY CODE SECTION 202.4 INDICATES WHAT |
| | TYPES OF WORK CAN BE BE DEDUCTED FROM THE CONTRACT |
| | VALUE THEN TAKEN TO SEE WHAT THE 20% DOLLAR VALUE WILL |
| | BE. THEN SHOW COMPLIANCE WITH 202.4.1 DISPROPORTIONATE |
| | COST. COSTS THAT MAY BE COUNTED AS EXPENDITURES |
| | REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF TRAVEL MAY |
| | INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING AN |
| | ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. ONCE THE |
| | DISPROPROTIONATE COST IS MET NO FURTHER ACCESSIBLE |
| | ELEMENTS WILL NEED TO BE UPGRADED UNDER THIS PERMIT. |
| | PLEASE SUPPLY A ITIMIZED COST BREAKDOWN FOR THE 20% OF |
| | PROPOSED WORK FOR ACCESSIBLE UPGRADES TO THIS BUILDING. |
| | |
| | 5A) SHEET A1.2 SHOWS NEW EXTERIOR WINDOWS (102 & 103) |
| | IN EXISITNG OPENINGS , THERE IS NO DETAILS IF WINDOW |
| | BUCKS ARE GOING TO BE INSTALLED OR IF THEY ARE GOING TO |
| | BE ANCHORED DIRECTLY TO THE CMU FILED UNITS? 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | 1710.10 WHERE THE WOOD BUCK THICKNESS IS 11/2 INCHES |
| | (38 MM) OR GREATER, THE BUCK SHALL BE SECURELY FASTENED |
| | TO TRANSFER LOAD TO THE MASONRY, CONCRETE OR OTHER |
| | STRUCTURAL SUBSTRATE AND THE BUCK SHALL EXTEND BEYOND |
| | THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME. WINDOW |
| | AND DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE MAIN |
| | FRAME OR BY JAMB CLIP OR SUBFRAME SYSTEM OR THROUGH THE |
| | FLANGE TO THE SECURED WOOD BUCK IN ACCORDANCE WITH THE |
| | MANUFACTURER?S PUBLISHED INSTALLATION INSTRUCTIONS. |
| | UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE |
| | INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT |
| | FULL SUPPORT OF THE FRAME IS PROVIDED. |
| | |
| | 5B) SHEET A1.2 SHOWS NEW EXTERIOR WINDOWS (102 & 103) |
| | IN EXISITNG OPENINGS, THIS SUBMITTAL NO PRODUCT |
| | APPROVALS WERE SUBMITTED. |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31) (B) WINDOWS |
| | |
| | 5C) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 5D) THE COVERSHEET INDICATES A VELOCITY PRESSURE OF |
| | 35PSF. PLEASE PROVIDE THE PRESSURES POSITIVE AND |
| | NEGATIVE FOR 24 SQ. FT. EXPOSURE "C" AT FOR 14 FT MEAN |
| | ROOF HEIGHT, IN VASD SINCE THE PRODUCT APPROVALS ARE IN |
| | VASD. 2014 FBC-B 1603.1.4. |
| | |
| | 6) UNDER THE LEVEL 3 ALTERATIONOF THE 2014 EXISITNG |
| | BUILDING CODE FOR ENERGY IT DIRECTS YOU TO THE 2014 |
| | ENERGY CODE. PLEASE PROVIDE THE VALUE OF THE STRUCTURE |
| | BEFORE WORK IS STARTED UNDER THIS PERMIT. IF THE |
| | BUILDING MEETS THE DEFINITION OF RENOVATION UNDER THE |
| | ENERG CODE IT CLASSIFIES AS TO WHAT IS REQUIRED FOR |
| | CODE COMPLIANCE. 2014 FBC-ENERGY: |
| | |
| | DEFINITIONS : RENOVATED BUILDING. A RESIDENTIAL OR |
| | NONRESIDENTIAL BUILDING UNDERGOING ALTERATION THAT |
| | VARIES OR CHANGES INSULATION, HVAC SYSTEMS, WATER |
| | HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS, |
| | PROVIDED THE ESTIMATED COST OF RENOVATION EXCEEDS 30 |
| | PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE. PLEASE |
| | PROVIDE COMPLIANCE WITH 2014 ENERGY CODE C401.2.1 WHICH |
| | METHOD? |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. |
| | |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |