Plan Review Notes
Plan Review Notes For Permit 15100589
Permit Number 15100589
Review Stop M
Sequence Number 2
Notes
Date Text
2015-12-02 07:44:131ST REVIEW 2014 MECHANICAL
 PERMIT #15100589
 12/2/15
  
 1) AS PREVIOUSLY REQUESTED IN THE FIRST REVIEW, PROVIDE
 AC COOLING AND HEATING CALCULATIONS IN ACCORDANCE WITH
 ACCA MANUAL N OR ASHRAE/ACCA STANDARD 183.
 2) HEAT LOAD SUMMARY ON SHEET M-1: A) THE SUMMARY WAS
 CALCULATED USING CARRIER SOFTWARE HOWEVER TRANE UNITS
 HAVE BEEN SELECTED. B) PROVIDE DOCUMENTATION VERIFYING
 THE PROGRAM IS ACCA OR ASHRAE APPROVED. C) THE TOTAL
 COOLING OF 6.5- TONS INDICATED IN THE SUMMARY IS MUCH
 LESS THAN THE 9-TONS OF COOLING TO BE PROVIDED TO THE
 TENANT SPACE USING THE THREE 3-TON RTU'S- PLEASE SEE
 SECTION C403.2.2 FBC-14 ENERGY CONSERVATION, EQUIPMENT
 AND SYSTEM SIZING.
 THE OUTPUT CAPACITY OF HEATING AND COOLING EQUIPMENT
 AND SYSTEMS SHALL NOT EXCEED THE LOADS CALCULATED IN
 ACCORDANCE WITH SECTION C403.2.1. A SINGLE PIECE OF
 EQUIPMENT PROVIDING BOTH HEATING AND COOLING SHALL
 SATISFY THIS PROVISION FOR ONE FUNCTION WITH THE
 CAPACITY FOR THE OTHER FUNCTION AS SMALL AS POSSIBLE,
 WITHIN AVAILABLE EQUIPMENT OPTIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  