| 2015-12-16 14:10:06 | REVIEW: FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 516-805-6700 |
| | [email protected] |
| | ALTERNATE CONTACT |
| | MIKE ALBARRAN |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |
| | PAGE E -1 |
| | |
| | 230.7 OTHER CONDUCTORS IN RACEWAY OR CABLE. CONDUCTORS |
| | OTHER THAN SERVICE CONDUCTORS SHALL NOT BE INSTALLED IN |
| | THE SAME SERVICE RACEWAY OR SERVICE CABLE. |
| | ( FUSED AND UNFUSED IN SAME CONDUIT. ) |
| | |
| | |
| | PROVIDE NEW RISER DIAGRAM AND LOAD CALCULATIONS FOR |
| | ENTIRE ELECTRICAL SYSTEM INCLUDING EXISTING. |
| | SHOW PROPER GROUNDING OF SERVICE TO INCLUDE |
| | SUPPLEMENTAL GROUND ROD AND WATER/METAL BONDING. NEC |
| | 250.53 |
| | ( DON'T FORGET NEC 250.94 INTERSYSTEM BONDING. ) |
| | |
| | 110.16 ARC-FLASH HAZARDWARNING. ELECTRICAL EQUIPMENT, |
| | SUCH AS SWITCHBOARDS, PANELBOARDS, INDUSTRIAL CONTROL |
| | PANELS, |
| | METER SOCKET ENCLOSURES, AND MOTOR CONTROL CENTERS, |
| | THAT |
| | ARE IN OTHER THAN DWELLING UNITS, AND ARE LIKELY TO |
| | REQUIRE |
| | EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE |
| | WHILE |
| | ENERGIZED SHALL BE FIELD MARKED TO WARN QUALIFIED |
| | PERSONS OF |
| | POTENTIAL ELECTRIC ARC FLASH HAZARDS. THE MARKING SHALL |
| | BE |
| | LOCATED SO AS TO BE CLEARLY VISIBLE TO QUALIFIED |
| | PERSONS BEFORE |
| | EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF |
| | THE EQUIPMENT. |
| | |
| | |
| | PAGE E-2 |
| | |
| | 406.9 RECEPTACLES IN DAMP OR WET LOCATIONS. |
| | (B) WET LOCATIONS. |
| | (1) 15- AND 20-AMPERE RECEPTACLES IN A WET LOCATION. |
| | 15- AND 20-AMPERE, 125- AND 250-VOLT RECEPTACLES |
| | INSTALLED IN |
| | A WET LOCATION SHALL HAVE AN ENCLOSURE THAT IS |
| | WEATHERPROOF |
| | WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. FOR |
| | OTHER |
| | THAN ONE- OR TWO-FAMILY DWELLINGS, AN OUTLET BOX HOOD |
| | INSTALLED |
| | FOR THIS PURPOSE SHALL BE LISTED, AND WHERE INSTALLED |
| | ON |
| | AN ENCLOSURE SUPPORTED FROM GRADE AS DESCRIBED IN |
| | 314.23(B) |
| | OR AS DESCRIBED IN 314.23(F) SHALL BE IDENTIFIED AS |
| | ?EXTRA-DUTY.? |
| | ALL 15- AND 20-AMPERE, 125- AND 250-VOLT |
| | NONLOCKING-TYPE |
| | RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE. |
| | |
| | |
| | NEC 410.30 LUMINAIRE SUPPORT |
| | SUSPENDED CEILINGS. FRAMING MEMBERS OF SUSPENDED |
| | CEILING SYSTEMS USED TO SUPPORT LUMINAIRES SHALL BE |
| | SECURELY |
| | FASTENED TO EACH OTHER AND SHALL BE SECURELY ATTACHED |
| | TO THE |
| | BUILDING STRUCTURE AT APPROPRIATE INTERVALS. LUMINAIRES |
| | SHALL |
| | BE SECURELY FASTENED TO THE CEILING FRAMING MEMBER BY |
| | MECHANICAL |
| | MEANS SUCH AS BOLTS, SCREWS, OR RIVETS. LISTED CLIPS |
| | IDENTIFIED FOR USE WITH THE TYPE OF CEILING FRAMING |
| | MEMBER( |
| | S) AND LUMINAIRE(S) SHALL ALSO BE PERMITTED. |
| | |
| | |
| | 600.5 BRANCH CIRCUITS. |
| | (A) REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL BUILDING |
| | AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| | SHALL BE PROVIDED WITH AT LEAST ONE OUTLET IN AN |
| | ACCESSIBLE |
| | LOCATION AT EACH ENTRANCE TO EACH TENANT SPACE FOR SIGN |
| | OR |
| | OUTLINE LIGHTING SYSTEM USE. THE OUTLET(S) SHALL BE |
| | SUPPLIED |
| | BY A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| | SUPPLIES |
| | NO OTHER LOAD. SERVICE HALLWAYS OR CORRIDORS SHALL NOT |
| | BE |
| | CONSIDERED ACCESSIBLE TO PEDESTRIANS. |
| | ( MISSING SIGN OUTLET BY SINGLE DOOR ADJACENT TO PANEL. |
| | ) |
| | |
| | PROVIDE COMPLIANCE FOR ALL LIGHTING IN ACCORDANCE WITH |
| | FBC ENERGY CODE C405 ( LIGHTING CONTROLS ) |