| Plan Review Notes For Permit 15100589 |
| Permit Number |
15100589 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-28 10:42:43 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15100589 | | | 10/28/15 | | | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW RTU'S IN COMPLIANCE WITH SECTION C403.2.1 FBC-14 | | | ENERGY CONSERVATION. | | | 2) PROVIDE ENERGY CALCULATIONS IN ACCORDANCE WITH | | | SECTION C101.4.3 FBC-14 ENERGY CONSERVATION. | | | 3) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR | | | SYSTEMS- SEE SECTION 606.2.1 & 606.2,.2 FBC-14 | | | MECHANICAL. | | | 4) WIND LOAD TIE DOWN ENGINEERING IS REQUIRED FOR | | | ATTACHING THE RTU'S AND CURBS TO THE STRUCTURE- REFER | | | TO SECTION 301.15 FBC-14 MECHANICAL. | | | 5) PROVIDE A CROSS-SECTION VIEW OF THE RTU AND CURB | | | INDICATING THE CURB MATERIALS, ROOF PATCHING DETAILS, | | | AND THE HEIGHT OF THE CURB ABOVE THE ROOF. | | | 6) PROVIDE A CONDENSATE DISPOSABLE PLAN SHOWING THE THE | | | TYPES AND SIZES OF CONDENSATE PIPING, PIPING RUNS, | | | PIPING SUPPORT, DISCHARGE LOCATIONS, AND PIPE | | | PROTECTION FROM UV DEGRADATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|