2015-10-28 10:42:431ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100589
 10/28/15
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW RTU'S IN COMPLIANCE WITH SECTION C403.2.1 FBC-14
 ENERGY CONSERVATION.
 2) PROVIDE ENERGY CALCULATIONS IN ACCORDANCE WITH
 SECTION C101.4.3 FBC-14 ENERGY CONSERVATION.
 3) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS- SEE SECTION 606.2.1 & 606.2,.2 FBC-14
 MECHANICAL.
 4) WIND LOAD TIE DOWN ENGINEERING IS REQUIRED FOR
 ATTACHING THE RTU'S AND CURBS TO THE STRUCTURE- REFER
 TO SECTION 301.15 FBC-14 MECHANICAL.
 5) PROVIDE A CROSS-SECTION VIEW OF THE RTU AND CURB
 INDICATING THE CURB MATERIALS, ROOF PATCHING DETAILS,
 AND THE HEIGHT OF THE CURB ABOVE THE ROOF.
 6) PROVIDE A CONDENSATE DISPOSABLE PLAN SHOWING THE THE
 TYPES AND SIZES OF CONDENSATE PIPING, PIPING RUNS,
 PIPING SUPPORT, DISCHARGE LOCATIONS, AND PIPE
 PROTECTION FROM UV DEGRADATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER