Plan Review Notes
Plan Review Notes For Permit 15100562
Permit Number 15100562
Review Stop B
Sequence Number 2
Notes
Date Text
2015-11-07 07:54:002ND REVIEW: FBC 2014 5TH ED.
  
 I RECEIVED AN EMAIL CONTAINING A PDF OF A CONTRACT
 PROPOSAL HOWEVER IT CONTAINED A DESCRIPTION OF WORK
 THAT WAS ONLY GENERAL AND DID NOT SATISFY THE
 REQUIREMENTS OF THE FIRST REVIEW TO SUPPLY INFORMATION
 ON CONSTRUCTION DOCUMENTS PER FBC 107.1.2. THERE IS
 BEPM&R WORK PROPOSED BUT NOT PLAN OR QUANTITY OR
 ADEQUATE DESCRIPTION AND THE ADDRESS OR LOCATION OF THE
 PROPOSED WORH IS NOT IDENTIFIED. BE ADVISED THAT THE
 PERMIT APPLICATIONS PROVIDED FOR ELECTRICAL, PLUMBING,
 MECHANICAL, & ROOFING WORK IN PART HAVE INFORMATION AS
 TO VALUE VS. THE PROPOSAL VALUE. FOR EXAMPLE, IS THE
 $1,200.00 LISTED ON THE HVAC APPLICATION IN ADDITION TO
 THE TOTAL OF $6,500.00?
  
 PLEASE PROVIDE INFORMATION AS REQUESTED IN THE FIRST
 AND THIS SECOND REVIEW OF YOUR SUBMITTAL. A COMPLETE
 REVIEW CANNOT BE PERFORMED.
  
 WHAT IS THE EXTENT OF THE TERMITE DAMAGE? IS THERE A
 REPORT? HAS AN ENGINEER LOOKED AT THE DAMAGE AND MADE A
 DETERMINATION AS TO THE LEVEL OF DAMAGE PURSUANT THE
 THE FBC EXISTING BUILDING VOLUME CHAPTER 2 DEFINITIONS
 OR CHAPTER 6 REPAIRS? ARE THE REPAIRS TO BE PER FBCE
 CHAPTER 6, IF SO, PLEASE PROVIDE INFORMATION AND
 SPECIFY.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  