| Plan Review Notes For Permit 15100556 |
| Permit Number |
15100556 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-06 14:34:29 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15100556 | | | 6/6/16 | | | | | | 1) INDICATE HOW MINIMUM VENTILATION (OUTDOOR AIR) WILL | | | BE PROVIDED TO THE NEW SPACE- SEE SECTION 401.2. PLEASE | | | NOTE THAT THE AC SCHEDULE INDICATES THE AREA SERVED AS | | | AN "OFFICE" BUT THE PLAN INDICATES "UTILITY ROOM". | | | | | | 2) THE 150 MPH WIND SHOWN IN THE "EQUIPMENT MOUNTING | | | DETAIL" ON M-1 IS INCORRECT, THE WIND SPEED IN WEST | | | PALM BEACH IS 170. PLEASE NOTE THAT THE ARCHITECT OF | | | RECORD HAS NOT PROVIDED COMPLETE WIND LOAD DESIGN | | | CRITERIA FOR ANY OF THE EXTERIOR IMPROVEMENTS- REFER TO | | | SECTION 1609.1.1 FBC-14 BUILDING- DETERMINATION OF WIND | | | LOADS. | | | | | | 3) M-1: THE CONDENSATE FROM THE INDOOR UNIT SHALL NOT | | | DRAIN INTO THE CITY SANITARY SYSTEM PER SEC. 90-126 WPB | | | CODE OR ORDINANCES. | | | | | | 4) M-1: THE RESCHECK COMPLIANCE CERTIFICATE LISTS THE | | | AC SYSTEM AT 19.2 SEER, HOWEVER THE AC SCHEDULE | | | INDICATES 17.2. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|