2016-06-06 14:34:291ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100556
 6/6/16
  
 1) INDICATE HOW MINIMUM VENTILATION (OUTDOOR AIR) WILL
 BE PROVIDED TO THE NEW SPACE- SEE SECTION 401.2. PLEASE
 NOTE THAT THE AC SCHEDULE INDICATES THE AREA SERVED AS
 AN "OFFICE" BUT THE PLAN INDICATES "UTILITY ROOM".
  
 2) THE 150 MPH WIND SHOWN IN THE "EQUIPMENT MOUNTING
 DETAIL" ON M-1 IS INCORRECT, THE WIND SPEED IN WEST
 PALM BEACH IS 170. PLEASE NOTE THAT THE ARCHITECT OF
 RECORD HAS NOT PROVIDED COMPLETE WIND LOAD DESIGN
 CRITERIA FOR ANY OF THE EXTERIOR IMPROVEMENTS- REFER TO
 SECTION 1609.1.1 FBC-14 BUILDING- DETERMINATION OF WIND
 LOADS.
  
 3) M-1: THE CONDENSATE FROM THE INDOOR UNIT SHALL NOT
 DRAIN INTO THE CITY SANITARY SYSTEM PER SEC. 90-126 WPB
 CODE OR ORDINANCES.
  
 4) M-1: THE RESCHECK COMPLIANCE CERTIFICATE LISTS THE
 AC SYSTEM AT 19.2 SEER, HOWEVER THE AC SCHEDULE
 INDICATES 17.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  