Plan Review Notes
Plan Review Notes For Permit 15100556
Permit Number 15100556
Review Stop E
Sequence Number 1
Notes
Date Text
2015-11-04 13:53:191ST REVIEW: FBC 2014 5TH ED. & RESIDENTIAL
  
 FBC 107 - PROVIDE AN ELECTRICAL PLAN TO DEMONSTRATE ANY
 PROPOSED ELECTRICAL IMPROVEMENTS.
  
 FBC 107 - PROVIDE A FLOOR PLAN TO SHOW THE USE OF THE
 SPACE AND THE ADJACENT SPACE WHICH COMMUNICATES WITH
 THE AREA. SHOW LIGHT & SWITCH AND RECEPTACLE LOCATIONS
  
 E3903.3 ADDITIONAL LOCATIONS.
 AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER. AT
 LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL
 BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR
 SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL
 ACCESS, INCLUDING OUTDOOR EGRESS DOORS FOR ATTACHED
 GARAGES AND DETACHED GARAGES WITH ELECTRIC POWER.
  
 E3903.4 STORAGE OR EQUIPMENT SPACES.
 IN ATTICS, UNDER-FLOOR SPACES, UTILITY ROOMS AND
 BASEMENTS, AT LEAST ONE LIGHTING OUTLET SHALL BE
 INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR
 CONTAIN EQUIPMENT REQUIRING SERVICING. SUCH LIGHTING
 OUTLET SHALL BE CONTROLLED BY A WALL SWITCH OR SHALL
 HAVE AN INTEGRAL SWITCH. AT LEAST ONE POINT OF CONTROL
 SHALL BE AT THE USUAL POINT OF ENTRY TO THESE SPACES.
 THE LIGHTING OUTLET SHALL BE PROVIDED AT OR NEAR THE
 EQUIPMENT REQUIRING SERVICING.
  
 E3902.2 GARAGE AND ACCESSORY BUILDING RECEPTACLES.
 ALL 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE
 RECEPTACLES INSTALLED IN GARAGES AND GRADE-LEVEL
 PORTIONS OF UNFINISHED ACCESSORY BUILDINGS USED FOR
 STORAGE OR WORK AREAS SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM IF APPLICABLE.
  
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
 FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  