| Plan Review Notes For Permit 15100485 |
| Permit Number |
15100485 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-15 17:04:22 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014) | | | | | | 1- ROOFING UNDERLAYMENT FLORIDA PRODUCT APPROVAL | | | FL5259-R24 SUBMITTED SAYS PENDING FBC APPROVAL. NEED TO | | | PROVIDE PRODUCT APPROVAL THAT IS APPROVED OR | | | MANUFACTURER MAY SUBMIT COMPLETE PRODUCT APPROVAL | | | PACKAGE FOR LOCAL PRODUCT APPROVAL. FAC | | | 61G20-3.002(33). | | | | | | 2- ROOF UNDERLAYMENT SUBMITTED: CLEARLY IDENTIFY WHICH | | | UNDERLAYMENT OPTION IS GOING TO BE USED TO VERIFY THE | | | DESIGN PRESSURES REQUIRED BY SEC. R301 OF | | | FBC-RESIDENTIAL 5TH EDITION (2014). | | | | | | 3- ROOF TILE ADHESIVE SUBMITTED: CLEARLY IDENTIFY WHICH | | | ADHESIVE PADDY PLACEMENT IS GOING TO BE USED TO VERIFY | | | THE DESIGN PRESSURES REQUIRED SEC. R301 OF | | | FBC-RESIDENTIAL 5TH EDITION (2014). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] | | | |
|