| 2015-10-30 13:16:16 | NFPA 14-6.4.5.4 FIRE DEPARTMENT CONNECTIONS SHALL BE | | | LOCATED NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST | | | FIRE HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY. |
|