| Plan Review Notes For Permit 15100422 |
| Permit Number |
15100422 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-22 10:12:10 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15100422 | | | 10/22/15 | | | | | | 1) THE COOLER AND FREEZER DIMENSIONS SHOWN IN THE PLAN | | | VIEW ARE INCORRECT: PLEASE PROVIDE CORRECT DIMENSIONS. | | | 2) PROVIDE COMPLETE EQUIPMENT SCHEDULES FOR THE | | | CONDENSERS AND EVAPORATOR INDICATING MAKES AND MODELS, | | | REFRIGERANT TYPES AND QUANTITIES, PHYSICAL AND | | | ELECTRICAL DATA ETC. | | | 3) PROVIDE WIND LOAD TIE DOWN ENGINEERING FOR THE | | | CONDENSERS AND ROOF TOP STANDS- SECTION 301.15 FBC-14 | | | MECHANICAL. | | | 4) REFRIGERANT PIPING: INDICATE TYPES AND SIZES OF | | | PIPING AND PIPE INSULATIONS, SHOW THE PIPING RUNS, AND | | | TRHU PENETRATION FIRESTOPPING DETAILS. | | | 5) SHOW THE DISCHARGE LOCATIONS OF THE EVAPORATOR | | | CONDENSATE LINES. | | | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WALK-IN | | | BOXES. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|