2015-10-22 10:12:101ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100422
 10/22/15
  
 1) THE COOLER AND FREEZER DIMENSIONS SHOWN IN THE PLAN
 VIEW ARE INCORRECT: PLEASE PROVIDE CORRECT DIMENSIONS.
 2) PROVIDE COMPLETE EQUIPMENT SCHEDULES FOR THE
 CONDENSERS AND EVAPORATOR INDICATING MAKES AND MODELS,
 REFRIGERANT TYPES AND QUANTITIES, PHYSICAL AND
 ELECTRICAL DATA ETC.
 3) PROVIDE WIND LOAD TIE DOWN ENGINEERING FOR THE
 CONDENSERS AND ROOF TOP STANDS- SECTION 301.15 FBC-14
 MECHANICAL.
 4) REFRIGERANT PIPING: INDICATE TYPES AND SIZES OF
 PIPING AND PIPE INSULATIONS, SHOW THE PIPING RUNS, AND
 TRHU PENETRATION FIRESTOPPING DETAILS.
 5) SHOW THE DISCHARGE LOCATIONS OF THE EVAPORATOR
 CONDENSATE LINES.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WALK-IN
 BOXES.
  