2015-10-26 20:03:22THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE ???2011
 EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH
 EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS
 APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED.
 1. YOU SHALL SUBMIT ELECTRICAL SPECIFICATIONS FOR THE
 PROPOSED UNIT.
 2. YOU SHALL PROVIDE A FEEDER DIAGRAM AS REQUIRED IN
 NEC 215.5. THIS SHALL INCLUDE SITE SPECIFIC LOAD CALCS
 AND CONDUCTOR SIZING AS PER NEC 440.
 3. YOU SHALL PROVIDE A SITE PLAN SHOWING THE LOCATION
 OF THE VARIOUS ELECTRICAL COMPONENTS OF THE UNITS.
 4. KEEP IN MIND THAT NEC 210.63 REQUIRES THAT THERE BE
 A 15 -20 AMP GFI OUTLET WITHIN 25? OF THE CONDENSING
 UNIT.
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.