2015-11-18 11:49:56MECHANICAL PROVISOS
 PERMIT #15100419
 11/18/15
  
 1) A NON-COMBUSTIBLE BACKING MATERIAL SHALL BE
 INSTALLED A MINIMUM OF 18 INCHES IN ALL DIRECTIONS
 AROUND THE TYPE 1 HOODS.
 2) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE UNIFRAX FYREWAP SHALL BE ON-SITE
 AT TIME OF INSPECTION.
 3) MIAMI-DADE NOA'S OR SITE SPECIFIC ENGINEERING FOR
 TIE DOWN OF THE EXHAUST AND SUPPLY FANS SHALL BE
 ON-SITE AT TIME OF INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER