| Plan Review Notes For Permit 15100419 |
| Permit Number |
15100419 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-11-18 11:49:56 | MECHANICAL PROVISOS | | | PERMIT #15100419 | | | 11/18/15 | | | | | | 1) A NON-COMBUSTIBLE BACKING MATERIAL SHALL BE | | | INSTALLED A MINIMUM OF 18 INCHES IN ALL DIRECTIONS | | | AROUND THE TYPE 1 HOODS. | | | 2) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | | INSTRUCTIONS FOR THE UNIFRAX FYREWAP SHALL BE ON-SITE | | | AT TIME OF INSPECTION. | | | 3) MIAMI-DADE NOA'S OR SITE SPECIFIC ENGINEERING FOR | | | TIE DOWN OF THE EXHAUST AND SUPPLY FANS SHALL BE | | | ON-SITE AT TIME OF INSPECTION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|