Plan Review Notes
Plan Review Notes For Permit 15100419
Permit Number 15100419
Review Stop M
Sequence Number 1
Notes
Date Text
2015-10-22 09:27:051ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100419
 10/22/15
  
 1) PLEASE REFER TO SECTION 508.1.1 FBC-14 MECHANICAL
 AND SHOW COMPLIANCE: MAKEUP AIR TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
 2) REFER TO SECTION 507.9 AND REVISE THE PLANS TO
 INDICATE COMPLIANCE: CLEARANCES FOR TYPE I HOOD.
 A TYPE I HOOD SHALL BE INSTALLED WITH A CLEARANCE TO
 COMBUSTIBLES OF NOT LESS THAN 18 INCHES (457 MM).
 EXCEPTION: CLEARANCE SHALL NOT BE REQUIRED FROM GYPSUM
 WALLBOARD OR 1/2-INCH (12.7 MM) OR THICKER CEMENTITIOUS
 WALLBOARD ATTACHED TO NONCOMBUSTIBLE STRUCTURES
 PROVIDED THAT A SMOOTH, CLEANABLE, NONABSORBENT AND
 NONCOMBUSTIBLE MATERIAL IS INSTALLED BETWEEN THE HOOD
 AND THE GYPSUM OR CEMENTITIOUS WALLBOARD OVER AN AREA
 EXTENDING NOT LESS THAN 18 INCHES (457 MM) IN ALL
 DIRECTIONS FROM THE HOOD.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 FYREWRAP, AND PROVIDE THE UL NUMBER ON THE PLANS FOR
 THE FIRESTOPPING ASSEMBLY.
 4) PROVIDE THE MAKES AND MODELS OF THE EXHAUST AND
 SUPPLY FANS AND SUBMIT NOA'S AND MANUFACTURER'S
 SPECIFICATIONS. PLEASE NOTE THAT THE WIND LOAD CALCS ON
 THE PLANS INDICATE FAN CURBS WHICH ARE NOT DEPICTED ON
 THE SECTION VIEWS OF THE FANS: PLEASE CLARIFY.
  