| 2015-10-22 09:27:05 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15100419 |
| | 10/22/15 |
| | |
| | 1) PLEASE REFER TO SECTION 508.1.1 FBC-14 MECHANICAL |
| | AND SHOW COMPLIANCE: MAKEUP AIR TEMPERATURE. |
| | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE |
| | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F |
| | (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS |
| | OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE |
| | HVAC SYSTEM. |
| | 2) REFER TO SECTION 507.9 AND REVISE THE PLANS TO |
| | INDICATE COMPLIANCE: CLEARANCES FOR TYPE I HOOD. |
| | A TYPE I HOOD SHALL BE INSTALLED WITH A CLEARANCE TO |
| | COMBUSTIBLES OF NOT LESS THAN 18 INCHES (457 MM). |
| | EXCEPTION: CLEARANCE SHALL NOT BE REQUIRED FROM GYPSUM |
| | WALLBOARD OR 1/2-INCH (12.7 MM) OR THICKER CEMENTITIOUS |
| | WALLBOARD ATTACHED TO NONCOMBUSTIBLE STRUCTURES |
| | PROVIDED THAT A SMOOTH, CLEANABLE, NONABSORBENT AND |
| | NONCOMBUSTIBLE MATERIAL IS INSTALLED BETWEEN THE HOOD |
| | AND THE GYPSUM OR CEMENTITIOUS WALLBOARD OVER AN AREA |
| | EXTENDING NOT LESS THAN 18 INCHES (457 MM) IN ALL |
| | DIRECTIONS FROM THE HOOD. |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | FYREWRAP, AND PROVIDE THE UL NUMBER ON THE PLANS FOR |
| | THE FIRESTOPPING ASSEMBLY. |
| | 4) PROVIDE THE MAKES AND MODELS OF THE EXHAUST AND |
| | SUPPLY FANS AND SUBMIT NOA'S AND MANUFACTURER'S |
| | SPECIFICATIONS. PLEASE NOTE THAT THE WIND LOAD CALCS ON |
| | THE PLANS INDICATE FAN CURBS WHICH ARE NOT DEPICTED ON |
| | THE SECTION VIEWS OF THE FANS: PLEASE CLARIFY. |
| | |