| Plan Review Notes For Permit 15100419 |
| Permit Number |
15100419 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-26 20:35:39 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION | | | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE ???2011 | | | EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH | | | EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS | | | APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED. | | | 1. YOU SHALL PROVIDE ELECTRICAL DATA FOR EACH OF THE | | | UNITS BEING INSTALLED. | | | 2. YOU SHALL SUBMIT A FEEDER DIAGRAM AS DESCRIBED IN | | | NEC 215.5. THE SHALL INCLUDE LOAD CALCS AND CONDUCTOR | | | SIZING. | | | THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN | | | MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED | | | FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED | | | TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG | | | WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE, | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY | | | APPRECIATED. | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | |
|