2015-11-13 08:20:11XFORMER ORC DOES APPEAR TO BE CONNECTED TO ANYTHING.
 PROVIDE SECONDARY CONNECTIONS AND LOADS.
 NOTES INDICATE DEMOLITION AND STATE EQUIPMENT IS
 EXISTING AND TO REMAIN. PLEASE EXPLAIN
 PROVIDE ORIGINAL PERMIT NUMBER UNDER WHICH THIS WORK
 WAS ORIGINALLY PERMITTED AND INSTALLED
 IS THE INTENT FOR INSTALLATION, DEMOLITION OR TO
 CORRECT UNPERMITTED WORK?
 ALL WIRING TO MAINTAIN REQUIRED SEPARATION PER NEC 517
 AND 700
 IT APPEARS EXISTING WIRING IS BEING RE-ROUTED TO
 PROVIDE PATIENT CARE SERVICES. ENSURE PROPER WIRING
 METHODS
 IS PANEL ORC ON SHEET E4-1 FED FROM XFORMER ORC? THE
 ONE LINE DRAWING DOES NOT SO INDICATE
 LUMINAIRES ON SHEET E3-1 HAVE FOOTNOTES "A, B, C" YET
 THIS INFORMATION DOES SEEM TO BE AVAILABLE, PLEASE
 EXPLAIN
 PROVIDE LISTING OF EQUIPMENT TO SHOW SUITABILITY FOR
 LOCATION AND USE
 PLEASE CLARIFY WHAT IS TO BE NEW, WHAT IS TO DEMOLISHED
 AND PROVIDE A COMPLETE DRAWING FOR "ORC"
 REVIEW NOT COMPLETE UNTIL THESE QUESTIONS CAN BE
 ANSWERED AND A COMPLETE DRAWING IS PROVIDED.
  