| Plan Review Notes For Permit 15100389 |
| Permit Number |
15100389 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-20 04:58:12 | 1) THE PERMIT APPLICATION NOTES " POOL FILTER | | | CHANGEOUT" YET THE PLANS SHOW A NEW SALT SYSTEM IS | | | BEING ADDED FOR THE POOL AND ALSO A PH FEEDER FOR THE | | | SPA. UPDATE THE DESCRIPTION OF WORK ON THE APPLICATION | | | TO INCLUDE THE SALT SYSTEM AND THE PH FEEDER SYSTEM. | | | THE JOB VALUE SHALL ALSO BE ADJUSTED TO INCLUDE THESE | | | ITEMS. WPB AMEND. TO THE FBC SEC. 109.3, 105.3.1. | | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION | | | MANUALS FOR THE CARTRIDGE FILTERS AND ALSO FOR THE SALT | | | SYSTEM FOR THE POOL.WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) THE PLANS SHOW A NEW STENNER PH FEEDER FOR THE SPA. | | | SUBMIT MANUF. SPEC SHETS / INSTALLATION MANUAL. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 4) THE SALT SYSTEM AND THE PH FEEDER SYSTEM/TANKS ARE | | | SHOWN ON THE PIPING DIAGRAM BUT NOT ON THE PLAN VIEW. | | | CLARIFY. | | | 5) THE MAXIMUM FILTRATION RATE IN GALLONS PER MINUTE | | | PER SQUARE FOOT OF FILTER AREA FOR THE CARTRIDGE | | | FILTERS SHALL BE 0.375 PER THE 2014 FBC | | | SEC.454.1.6.5.5.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|