2015-10-23 11:32:39BUILDING PLAN REVIEW
 W. P. B. REVISION: 15100372
 W. P. B. PERMIT: 14080811
 ADD: 5300 EAST AVE.
 CONT: TRILLIUM CONSTRUCTION
 TEL: (561)371-6825
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. OCT. 23/2015
 ACTION: DENIED
  
 1) THIS AREA IS KNOWN FOR QUESTIONABLE SOILS BEARING
 VALUE. PLEASE PROVIDE A SOILS REPORT WITH THE MINIMUM
 SAFE BEARING VALUE. 2010 FBC-B 1803.5.2. QUESTIONABLE
 SOILS.
  
 2A) SHEET A1 SHOWS A NEW PORTE COCHERE. THIS IS A DROP
 OFF AND PICK UP ZONE THAT WILL NEED TO SHOW COMPLIANCE
 WITH: 2010 FBC-ACCESSIBILITY SECTION 503.2 VEHICLE
 PULL-UP SPACE, 96 INCHES WIDE BY 20 FEET LONG MINIMUM.
  
 2B) 2010 FBC-ACCESS AISLE 503.3.
  
 2C) 503.3.1 ACCESS AISLES SERVING VEHICLE PULL-UPSPACES
 SHALL BE 60 INCHES
  
 2D) 503.3.2 LENGTH, ACCESS AISLE SHALL EXTEND THE FULL
 LENGTH OF THE VEHICLE PULL-UP SPACES THEY SERVE.
  
 2E) MARKING. ACCESS AISLES SHALL BE MARKED SO AS TO
 DISCOURAGE PARKING IN THEM.
  
 3) SHEET A1 VERSES SHEET D. ON THE D- DEMOLITION SHEET
 NOTE # 10 INDICATES THIS DOOR OPENING TO BE REMOVE
 EXISITNG ENTRANCE DOOR. SHEET A1 INDICATES THIS OPENING
 AS E-2, A EXISITNG OPENING. THE PERMIT ISSUED SET OF
 PLANS INDICATES A PAIR OF 3'-0" DOORS FOR THE EXISITNG
 OPENING. THIS WILL BE A NEW DOOR AND SIDELIGHT, NO
 INFORMATION ON THE SIZE OF THE DOOR, TYPE OF DOOR,
 THERE IS NO DOOR SCHEDULE WITH THIS INFORMATION NOR IS
 THERE A PRODUCT APPROVAL FOR THIS NEW DOOR AND SIDE
 LIGHT.
 THIS IS IS ADJACENT TO THE AMBULANCE ENTRANCE DROP OFF
 ZONE, WILL THIS DOOR BE OVERSIZED IN WIDTH FOR
 STRETCHERS? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4A) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 4B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5) SHEET 2 SERIES AND SHEET 4 THE ELEVATIONS ALL
 INDICATE THE USE OF STONE VENEER OF CMU CONSTRUCTION,
 THE PLANS INDICATE TO BE INSTALLED TO THE MANUFACTURES
 SPECIFICATIONS.
 THE PLANS DO NOT PROVIDE DIRECTION IF WHICH DIRECTION
 CODE COMPLIANCE IS TO BE ACHIEVED. 1405.6 ANCHORED
 MASONRY VENEERS, 1405.7 STONE VENEERS OR 1405.10
 ADHERED MASONRY VENEERS.
  
 6) SHEET A2.1 :
  
 6A) INDICATES THE USE OF A GLASS CANOPY SYSTEM. PLEASE
 PROVIDE COMPLIANCE WITH 2010 FBC-B 2405.2 ALLOWABLE
 GLAZING MATERIALS AND LIMITATIONS. PLEASE PROVIDE
 DOCUMENTATION OF CODE COMPLIANCE. 107.3.5.5.1.1 MINIMUM
 PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS &
 STRUCTURES.
  
 6B) THE PORTE CACHERE INDICATES THE ROOFING TO BE
 BUILT-UP ROOFING WITH TAPPERED INSULATION. PLEASE
 PROVIDE COMPLIANCE WITH:
  
 COMPONENTS & CLADDING.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 6C) SHEET S-1 SHOWS BOTH THE VULT AND VASD PRESSURES.
 THE CHART SHOWING THE PRESSURES HAS THE SAME PRESSURES
 FOR ZONE 2 AND ZONE 3.
 SHEET A2.1 DETAIL A/A-5 INDICATES A CUT SECTION THROUGH
 THE CANOPY NO 3 FOOT PARAPET.
 SHEET A2.2 DETAIL 6/ A6 SHOWSA CUT SECTION THROUGH THE
 AMBULANCE CANOPY, THERE IS NO 3 FOOT PARAPET THERE
 EITHER.
 PLEASE ADJUST THE ZONE 3 PRESSURES UP SINCE IN NEITHER
 CASE CAN YOU TAKE THE REDUCTION IS PRESSURES FOR A 3
 FOOT HIGH PARAPET.
  
 7) SHEET A2.2 ALSO INDICATES THE INSTALATION OF A
 PRE-ENGINEREED ALUMINUM CANOPY. PLEASE PROVIDE A DESIGN
 OF HOW THE PRE-ENGINEERED CANOPY IS TO BE HELD IN
 PLACE?
 WHAT TYPE OF STRUCTURAL ELEMENTS ARE GOING TO BE
 IMPLEMENTED? ADDITIONAL INFORMATION IS R EQUIRED.
 107.3.5.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS & STRUCTURES.
  
 8) SHEET A6 DETAIL # 3 SHOWS A CLEAR HEIGTH OF 11'-0"
 UNDER THIS CANOPY, IS THIS HIGH ENOUGH CLEAR HEIGTH FOR
 A AMBULANCE TO BACK IN UNDER? NOTE A CODE ISSUE, JUST A
 QUESTION.
  
 9A) SHEET A-5 & S-2 BOTH SHOW THE USE OF DENSGLASS
 SHEATHING ON THE NEW FRONT ENTRY FEATURE. PLEASE
 PROVIDE THE PRODUCT APPROVAL FOR DENSEGLASS AND
 LIMITATIONS OF USE. IF THE PRODUCT APPROVAL HAS MORE
 THAN ONE SUB-SYSTEM PLEASE CIRCLE THE SUB-SYSTEM AND
 ASSOCIATED PRESSURES. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS: (31)(C) PANEL
 WALLS.
  
 9B) SHEET A5 & S2 SHOW THE USE OF STONE VENEER OVER
 DENSE-GLASS SHEATHING. PLEASE PROVIDE HOW THE STONE
 VENEER IS TO BE ADHEERED/ ATTACHED TO THE DENSEGLASS
 AND DOES EITHER PRODUCT HAVE LIMITATIONS AGAINST SUCH
 INSTALATIONS. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 9C) PLEASE PROVIDE THE ROOFING PRODUCT APPROVAL FOR THE
 TIE IN OF THE ROOFING AND THE FRONT ENTRY FEATURE.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  