| Plan Review Notes For Permit 15100349 |
| Permit Number |
15100349 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-14 14:48:45 | 1ST REVIEW: FBC 2010 MECHANICAL | | | REVISION #15100349 | | | MASTER #15020941 | | | | | | 1) THE NEW RETURN GRILLS AND 18 " TRANSFER DUCT IN THE | | | OPEN AREA SEEM TO BE LOCATED IN THE WRONG LOCATION. | | | PROVIDE A DUCTED RETURN FROM THE WORSHIP ROOM BACK TO | | | THE RELOCATED AHU FOR BALANCED RETURN AIR- SECTION | | | 601.2 FBC-10 MECHANICAL, | | | 2) CLARIFY IF A DUCT SMOKE DETECTOR IS BEING RELOCATED | | | WITH THE AHU AND PROVIDE DETAILS. | | | 3) SHOW THE REQUIRED CLEARANCE SPACE DIMENSIONS AROUND | | | THE AIR HANDLER IN THE CLOSET- REFER TO SECTION | | | 603.1.3. | | | 4) INDICATE THE TYPE AND SIZE OF DOOR FOR THE AHU | | | CLOSET- SEE SECTIONS 306.1 AND 603.1. | | | 5) PROVIDE A REVISED ELECTRICAL PLAN SHOWING THE NEW | | | CIRCUITRY FOR THE RELOCATED AIR HANDLER . | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|