| Notes |
| Date |
Text |
| 2015-10-13 18:25:12 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE RAS 117 CALCULATIONS ARE INCORRECT. THE CORNER | | | REQUIRES FASTENER SPACING OF 4" OC @ LAPS AND FOUR (4) | | | EQUALLY SPACED STAGGERED ROWS @4" OC IN THE CENTER OF | | | THE SHEET. THE ENGINEERING THAT WAS SUBMITTED HAS ONLY | | | (3) ROWS IN THE CENTER OF THE SHEET. FBC 107.2.1 |
|