Plan Review Notes
Plan Review Notes For Permit 15100322
Permit Number 15100322
Review Stop P
Sequence Number 1
Notes
Date Text
2015-12-22 14:19:21 
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 1. CONTRACTOR PROVIDED SIGNED AND SEALED LETTER STATING
 NO PLUMBING ABOVE FIRST FLOOR .
 APPROVED TO USE AAV.
2015-10-22 15:22:23 
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. WHEN YOU USE AN AAV ON A BRACH DRAIN THAT IS LOWER
 THAN 4 FLOORS FROM THE TOP A RELIEF VENT IS REQUIRED.
 PER FBCP SEC 917.3.2 RELIEF VENT.
  
 WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR
 BRANCH INTERVALS FROM THE TOP OF THE STACK, THE
 HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT
 THAT SHALL CONNECT TO A VENT STACK OR STACK VENT, OR
 EXTEND OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE
 STACK AND THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED
 TO THE HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL
 BE SIZED IN ACCORDANCE WITH SECTION 916.2 AND INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL
 BE PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES.
  
  
  
  
  
  
  
  