| Plan Review Notes For Permit 15100322 |
| Permit Number |
15100322 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-22 14:19:21 | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | 1. CONTRACTOR PROVIDED SIGNED AND SEALED LETTER STATING | | | NO PLUMBING ABOVE FIRST FLOOR . | | | APPROVED TO USE AAV. | | 2015-10-22 15:22:23 | | | | | | | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. WHEN YOU USE AN AAV ON A BRACH DRAIN THAT IS LOWER | | | THAN 4 FLOORS FROM THE TOP A RELIEF VENT IS REQUIRED. | | | PER FBCP SEC 917.3.2 RELIEF VENT. | | | | | | WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR | | | BRANCH INTERVALS FROM THE TOP OF THE STACK, THE | | | HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT | | | THAT SHALL CONNECT TO A VENT STACK OR STACK VENT, OR | | | EXTEND OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL | | | CONNECT TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE | | | STACK AND THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED | | | TO THE HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL | | | BE SIZED IN ACCORDANCE WITH SECTION 916.2 AND INSTALLED | | | IN ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL | | | BE PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES. | | | | | | | | | | | | | | | | | | | | | | | | |
|