| Plan Review Notes For Permit 15100321 |
| Permit Number |
15100321 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-21 16:58:19 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. G101, THE 1 HR CORRIDOR RATING AT THE MAIL ROOM 117 | | | IS NOT CONTINUOUS, FBC 1018. | | | | | | 2. G101, PROVIDE INFORMATION REGARDING THE COILING FIRE | | | DOORS AND OPERATION. THE MAIL ROOM DOES NOT HAVE AN | | | EGRESS DOOR, AND THE MEANS OF EGRESS PATH SHOWS THE | | | OCCUPANT GOING THROUGH THE COILING FIRE DOOR FROM THE | | | ELEVATOR LOBBY 186 TO THE VESTIBLUE 122, FBC 107. | | | | | | 3. A101A SPECIFIES A 20 MINUTE CURTAIN AT THE MAIL ROOM | | | AND 45 MINUTE AT THE LIVING ROOM, G101 SPECS A 60 | | | MINUTE; PLEASE CORRELATE. | | | | | | |
|